No.
Name
Setting Range
Default
L4-03
Speed Agree Detection Level (+/-)
-400.0 to 400.0 Hz
0.0 Hz
L4-04
Speed Agree Detection Width (+/-)
0.0 to 20.0 Hz
Determined by
A1-02
Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection on page 87
, Settings 13, 14, 15,
and 16.
n
L4-05: Frequency Reference Loss Detection Selection
The drive can detect a loss of an analog frequency reference from input A1, A2, or A3. Frequency reference loss is detected
when the frequency reference drops below 10% of the reference or below 5% of the maximum output frequency within 400
ms.
100%
400 ms
Analog
frequency
reference
Loss of
Reference
output
time
10%
ON
OFF
Figure 1.69 Loss of Reference Function
Set H2-01 or H2-02 to C for a digital output to trigger when frequency reference loss occurs.
for details on setting the output function.
Parameter L4-05 selects the operation when a frequency reference loss is detected.
No.
Name
Setting Range
Default
L4-05
Frequency Reference Loss Detection Selection
0, 1
1
Setting 0: Stop. Drive stops when the frequency reference is lost.
Setting 1: Run. Drive continues operation according to the setting of L4-06.
The drive will continue operation at the percent of the previous frequency value set to parameter L4-06. When the external
frequency reference value is restored, the operation is continued with the frequency reference.
n
L4-06: Frequency Reference at Reference Loss
Sets the frequency reference level at which the drive runs when L4-05 = 1 and when detecting a reference loss. The value is
set as a percentage of the frequency reference before the loss was detected.
No.
Name
Setting Range
Default
L4-06
Frequency Reference at Reference Loss
0.0 to 100.0%
80.0%
n
L4-07: Speed Agree Detection Selection
Determines when frequency detection is active using parameters L4-01 through L4-04.
No.
Name
Setting Range
Default
L4-07
Speed Agree Detection Selection
0, 1
0
Setting 0: No Detection during baseblock
Setting 1: Detection always enabled
u
L5: Fault Restart
After a fault has occurred, Fault Restart attempts to automatically restart the motor and continue operation instead of stopping.
The drive can perform a self-diagnostic check and resume the operation after a fault has occurred. If the self-check is successful
and the cause of the fault has disappeared, the drive restarts by first performing Speed Search (
Note:
1.
The wiring sequence should remove the Forward/Reverse command when a fault is triggered and output is shut off.
1.8 L: Protection Functions
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
117
1
Parameter Details