Setting 0: Ramp to Stop
The drive stops the motor using the deceleration time 1 set in parameter C1-02.
Setting 1: Coast to Stop
The drive output is switched off and the motor coasts to stop.
Setting 2: Fast Stop
The drive stops the motor using the Fast Stop time set in parameter C1-09.
n
L1-05: Motor Temperature Input Filter Time (PTC input)
Sets a filter on the PTC input signal to prevent erroneous detection of a motor overheat fault.
No.
Name
Setting Range
Default
L1-05
Motor Temperature Input Filter Time (PTC input)
0.00 to 10.00 s
0.20 s
n
L1-08: oL1 Current Level
Sets the reference current for motor thermal overload detection for motor 1 in amperes. When L1-08 is set to 0.0 A (default),
parameter E2-01 (E5-03 in PM control modes) is used as the reference for motor overload protection. When L1-08
≠
0.0 A,
the set value is used as the reference for motor overload protection.
No.
Name
Setting Range
Default
L1-08
oL1 Current Level
0.0 A or 10 to 150% of drive
rated current
<1> <2>
0.00 A
<1> Display is in the following units:
2
o
0028, 2
o
0042, and 4
o
0011 to 4
o
0027: 0.01 A units
2
o
0054 to 2
o
0248 and 4
o
0034 to 4
o
0414: 0.1 A units
<2> Cannot be set to a value smaller than 10% of drive rated current when the current level is set to a value greater than 0.0 A.
n
L1-13: Continuous Electrothermal Operation Selection
Determines whether to hold the current value of the electrothermal motor protection (L1-01) when the power supply is
interrupted.
No.
Name
Setting Range
Default
L1-13
Continuous Electrothermal Operation Selection
0 to 2
1
Setting 0: Disabled
Setting 1: Enabled
Setting 2: Enable Using Real Time Clock (HOA Keypad)
Stores value and integrates (resets) down the oL value based on real time.
u
L2: Momentary Power Loss Ride-Thru
n
L2-01: Momentary Power Loss Operation Selection
When a momentary power loss occurs, the drive can automatically return to the operation it was performing prior to the power
loss based on certain conditions.
No.
Name
Setting Range
Default
L2-01
Momentary Power Loss Operation Selection
0 to 2
0
Setting 0: Disabled
If a momentary power loss occurs, a power supply frequency fault (Fdv) is detected and the drive output is turned OFF. The
motor coasts to stop.
Setting 1: Recover within L2-02
When a momentary power loss occurs, the drive output will be shut off. If the power returns within the time set to parameter
L2-02, the drive will perform Speed Search and attempt to resume operation. If power does not return within this time, it will
trigger a Uv1 fault.