If a lower reference than this value is entered, the drive will run at the limit set to d2-02. If the drive is started with a lower
reference than d2-02, it will accelerate up to d2-02.
No.
Parameter Name
Setting Range
Default
d2-02
Frequency Reference Lower Limit
0.0 to 110.0%
0.0%
Internal frequency
reference
d2-01
Operating
range
Frequency Reference Upper Limit
Set frequency reference
Frequency Reference Lower Limit
d2-02
Figure 4.20 Frequency Reference: Upper and Lower Limits
n
E1-01: Input Voltage Setting
Adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.). Set this parameter to the nominal
voltage of the AC power supply.
NOTICE: Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the
protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.
No.
Parameter Name
Setting Range
Default
E1-01
Input Voltage Setting
<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
E1-01 Related Values
The input voltage setting determines the overvoltage and undervoltage detection levels, the KEB function, and the overvoltage
suppression function.
Voltage
Setting Value of E1-01
(Approximate Values)
Uv Detection Level (L2-05)
200 V Class
All settings
190 V
400 V Class
Setting > 460 V
440 V
Setting
≥
400 V
380 V
Setting < 400 V
350 V
n
V/f Pattern Settings E1-04 to E1-13
If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04
through E1-13. To create a new V/f pattern, set E1-03 to F.
Refer to V/f Pattern on page 135
pattern.
Note:
Certain E1-
oo
parameters might not be visible depending on the control mode.
Refer to Parameter List on page 281
for details.
No.
Parameter Name
Setting Range
Default
E1-04
Maximum Output Frequency
40.0 to 240.0 Hz
E1-05
Maximum Voltage
0.0 to 255.0 V
E1-06
Base Frequency
0.0 to 240.0 Hz
E1-07
Middle Output Frequency
0.0 to 240.0 Hz
E1-08
Middle Output Frequency Voltage
E1-09
Minimum Output Frequency
0.0 to 240.0 kHz
E1-10
Minimum Output Frequency Voltage
E1-11
Middle Output Frequency 2
0.0 to 240.0 Hz
E1-12
Middle Output Frequency Voltage 2
0.0 V
4.7 Basic Drive Setup Adjustments
134