S3-03: Secondary PI Display Digits
Sets the decimal place display for secondary PI units.
No.
Name
Setting Range
Default
S3-03
Secondary PI Display Digits
0 to 3
2
Setting 0: No Decimal Places
Setting 1: One Decimal Place
Setting 2: Two Decimal Places
Setting 3: Three Decimal Places
n
S3-04: Secondary PI Unit Selection
Sets units for secondary PI control function.
No.
Name
Setting Range
Default
S3-04
Secondary PI Unit Selection
0 to 15
15
Setting 0: Inch of Water (WC)
Setting 1: Pounds per Square Inch (PSI)
Setting 2: Gallons per Minute (GPM)
Setting 3: Degrees Fahrenheit (F)
Setting 4: Cubic Feet per Minute (CFM)
Setting 5: Cubic Meters per Hour (CMH)
Setting 6: Liters per Hour (LPH)
Setting 7: Liters per Second (LPS)
Setting 8: Bar (Bar)
Setting 9: Pascals (Pa)
Setting 10: Degrees Celsius (C)
Setting 11: Meters (Mtr) (Ft: Feet)
Setting 12: Liters per Minute (LPM)
Setting 13: Cubic Meters per Minute (CMM)
Setting 14: No Unit
Setting 15: Percentage (%)
n
S3-05: Secondary PI Setpoint Value
Sets the secondary PI controller target value
No.
Name
Setting Range
Default
S3-05
Secondary PI Setpoint Value
0.00 to 600.00
0.00
<1> Upper limit is S3-02, decimal place holder is determined by S3-03.
<2> Unit is determined by S3-04.
n
S3-06: Secondary PI Proportional Gain Setting
Sets the proportional gain of the secondary PI controller. A setting of 0.00 disables P control.
No.
Name
Setting Range
Default
S3-06
Secondary PI Proportional Gain Setting
0.00 to 25.00
1.00
n
S3-07: Secondary PI Integral Time Setting
Sets the integral time for the secondary PI controller. A setting of 0.0s disables integral control.
No.
Name
Setting Range
Default
S3-07
Secondary PI Integral Time Setting
0.0 to 360.0 s
1.0 s
1.11 S: Special Parameters
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
141
1
Parameter Details