Electrical Characteristics
The following table provides electrical characteristics for network
communication cables.
Table 1: Line Parameters
Parameter
Line A
Line B
Impedance
135 ...165 W
(3 to 20 Mhz)
100 ...130 W
(f >100kHz)
Capacity
<30 pF/m
<60 pF/m
Resistance
<110 W /km
-
Wire gauge
>0,64 mm
>0,53 mm
Conductor area
>0,34 mm
>0,22 mm
Transmission Line Lengths
The following table shows the cable lengths to be used at different
transmission speeds.
Table 2:
Line Lengths for Different Transmission Speeds
Baud rate (kbit/s)
9.6
19.2 93.75 187.5
500
1500
3000-
12000
Length line A (m)
1200 1200 1200 1000
400
200
100
Length line B (m)
1200 1200 1200
600
200
-
-
Connection Cables
The following are examples of cables that may be used to connect
XtraDrive-DP to a PROFIBUS network:
✦
Desina - PROFIBUS cable - Catalog no. 3DRX 22X 02R
✦
Siemens - PROFIBUS cable - Catalog no. V45467-G16-C85-G1