6 Parameter 

Settings 

6.1 

J7 to J1000

 

Parameter Correspondence for Drive Replacement   

・ 

Before setting up other parameters, make sure that C6-01 is set to “0” (Heavy Duty). Refer to the 
Technical manual for details on the Normal and Heavy Duty selection. 

・ 

The given voltage values are valid for 200 V units. For 400 V units the values have to be doubled. 

 

 

VAN-V07007E

 

 [J7

J1000] Replacement Instructions 

9/16

J7 

J1000 

                          Drive 
Function/ 
Parameter 

Parameter 

No. 

Initial Value

Parameter 

No. 

Initial Value

Comments 

Parameter access 
level 

A1-01 2 

Initialization 

A1-03 0 

Run Command in 
Programming Mode 

b1-08 0 

Fault history U2 
initialization 

n01 1 

o4-11 0 

J7 J1000 

n01

0 A1-01

n01

1 A1-01

n01

5 A1-01

b1-08

n01

6 o4-11

n01

8 A1-03

2220

n01

9 A1-03

3330

 

RUN command source 
selection 

n02 0 b1-02  1 

J7 J1000 

n02

0 b1-02

n02

b1-02

n02

2 b1-02

 

Frequency reference 
source selection 

n03 0 b1-01  1 

J7 J1000 

n03

0

b1-01

3  (AI-V3/J 

option required) 

n03

1

b1-01

n03

2

b1-01

1 and H3-01

0  

n03

3

b1-01

1 and H3-01

n03

4

b1-01

1 and H3-01

n03

6

b1-01

2  (SI-485/J) 

option required) 

 
When using A1 as frequency reference 
input, make sure to set DIP switch S1 
properly (voltage or current input). 

Stop method selection 

n04 0 b1-03  0 

J7 J1000 

n04

0 b1-03

n04

1 b1-03

 

Reverse run prohibit 
selection 

n05 0 b1-04  0 

J7 J1000 

n05

0 b1-04

n05

1 b1-04

 

Digital Operator STOP 
key function 

n06 0 o2-02  1 

J7 J1000 

n06

0 o2-02

n06

1 o2-02

 

Frequency reference in 
local mode 

n07 0  - 

-  - (no operator panel potentiometer) 

Frequency reference 
from operator ENTER 
key selection 

n08 0 o2-05  0 

J7 J1000 

n08

0 o2-05

n08

1 o2-05

 

Max. output frequency 

n09 

60.0 Hz 

E1-04 

60.0 Hz 

 

Max. output voltage 

n10 

200 V * 

E1-05 

200 V * 

* Values for a 400 V class drive are double.

Base frequency 

n11 60.0Hz E1-06 60.0 

Hz 

 

Mid. output frequency 

n12 1.5Hz E1-07 3.0 

Hz 

 

Mid. output voltage 

n13 

12 V * 

E1-08 

16.0 V * 

* Values for a 400 V class drive are double.

Содержание VS MINI J7

Страница 1: ...tric Wire Differences 5 3 5 Control terminal sizes and wire sizes 6 4 Dimensions 7 5 Options Replacement 8 6 Parameter Settings 9 6 1 J7 to J1000 Parameter Correspondence for Drive Replacement 9 6 2 J...

Страница 2: ...to make sure that it is compliant to the standard specification no special firmware Wire Length In the J7 drive main terminals are located at the top of the drive The J1000 drive has all main terminal...

Страница 3: ...it works properly Is an EMC Filter installed EMC filters installed with a J7 can partially used with a J1000 For details on filter replacement contact your sales agent Before using the old J7 filter...

Страница 4: ...lti function input 1 1 Run forward 0 Stop S2 Multi function input 2 1 Run reverse 0 Stop S3 Multi function input 3 J7 Fault Reset J1000 Ext Fault S4 Multi function input 4 J7 Ext Fault J1000 Fault Res...

Страница 5: ...U T1 V T2 W T3 1 2 B1 B2 2 J1000 2A0010 2 terminals M4 1 2 1 5 2 0 5 5 3 5 J7 22P2 R L1 S L2 T L3 U T1 V T2 W T3 1 2 M3 5 0 8 1 0 J1000 2A0012 R L1 S L2 T L3 U T1 V T2 W T3 1 2 B1 B2 2 terminals M4 1...

Страница 6: ...S L2 T L3 U T1 V T2 W T3 1 2 2 J7 43P0 43P7 M4 1 2 1 5 2 0 5 5 3 5 R L1 S L2 T L3 U T1 V T2 W T3 1 2 B1 B2 2 Three Phase 400V J1000 4A0009 4A0011 2 terminals M4 1 2 1 5 2 0 5 5 3 5 3 5 Control termina...

Страница 7: ...29 137 5 Single Phase 200V B1P50 BA0010B 108 128 154 108 128 154 Not required 20P10 2A0001B 20P20 2A0002B 70 76 20P40 2A0004B 102 108 20P70 2A0006B 68 122 68 128 21P50 2A0010B 129 129 22P20 2A0012B 10...

Страница 8: ...Interface for RS 422 485 communication Memobus SI 485 J7 SI 485 J Remote operator without potentiometer JVOP 146 JVOP 182 Remote operator with potentiometer JVOP 144 not available Extension cable 1 m...

Страница 9: ...eference source selection n03 0 b1 01 1 J7 J1000 n03 0 b1 01 3 AI V3 J option required n03 1 b1 01 0 n03 2 b1 01 1 and H3 01 0 n03 3 b1 01 1 and H3 01 2 n03 4 b1 01 1 and H3 01 3 n03 6 b1 01 2 SI 485...

Страница 10: ...tely for each ride profile section Multi speed ref 1 n21 0 0Hz d1 01 0 00 Hz Multi speed ref 2 n22 0 0Hz d1 02 0 00 Hz Multi speed ref 3 n23 0 0Hz d1 03 0 00 Hz Multi speed ref 4 n24 0 0Hz d1 04 0 00...

Страница 11: ...n36 39 10 H1 02 H1 05 6 n36 39 11 H1 02 H1 05 7 n36 39 12 H1 02 H1 05 8 n36 39 13 H1 02 H1 05 9 n36 39 14 H1 02 H1 05 61 n36 39 15 H1 02 H1 05 62 n36 39 16 H1 02 H1 05 A n36 39 17 H1 02 H1 05 1 n36 39...

Страница 12: ...AM function selection n44 0 H4 01 102 J7 J1000 n44 0 H4 01 102 n44 1 H4 01 103 Analog output AM gain n45 1 00 H4 02 100 0 Set H4 02 n45 100 Carrier frequency selection C6 02 o2 04 dep Carrier frequenc...

Страница 13: ...01 3 n59 3 L6 01 2 n59 4 L6 01 4 Over torque detection level n60 160 L6 02 150 Over torque detection time n61 0 1 s L6 03 0 1 s Frequency reference hold selection up down function n62 0 d4 01 0 J7 J10...

Страница 14: ...8 38 0 n75 1 L8 38 1 COPY function selection n76 rdy o3 01 0 Possible with copy unit or remote operator READ prohibit selection n77 0 o3 02 0 Fault History n78 U2 01 02 In the J1000 the last current f...

Страница 15: ...0 type JA x Output power kVA Output current A Carrier frequency kHz Output power kVA Output current A Carrier frequency kHz 0 1 B0P1 BA0001 0 3 0 8 0 3 0 8 0 2 B0P2 BA0002 0 6 1 6 0 6 1 6 0 4 B0P4 BA0...

Страница 16: ...Revision History Rev No Date Modification 21 Dec 07 First Edition VAN V07007E J7 J1000 Replacement Instructions 16 16...

Отзывы: