6 Parameter
Settings
6.1
J7 to J1000
Parameter Correspondence for Drive Replacement
・
Before setting up other parameters, make sure that C6-01 is set to “0” (Heavy Duty). Refer to the
Technical manual for details on the Normal and Heavy Duty selection.
・
The given voltage values are valid for 200 V units. For 400 V units the values have to be doubled.
VAN-V07007E
[J7
→
J1000] Replacement Instructions
9/16
J7
J1000
Drive
Function/
Parameter
Parameter
No.
Initial Value
Parameter
No.
Initial Value
Comments
Parameter access
level
A1-01 2
Initialization
A1-03 0
Run Command in
Programming Mode
b1-08 0
Fault history U2
initialization
n01 1
o4-11 0
J7 J1000
n01
→
0 A1-01
→
0
n01
→
1 A1-01
→
2
n01
→
5 A1-01
→
2
b1-08
→
1
n01
→
6 o4-11
→
1
n01
→
8 A1-03
→
2220
n01
→
9 A1-03
→
3330
RUN command source
selection
n02 0 b1-02 1
J7 J1000
n02
→
0 b1-02
→
0
n02
→
1
b1-02
→
1
n02
→
2 b1-02
→
2
Frequency reference
source selection
n03 0 b1-01 1
J7 J1000
n03
→
0
b1-01
→
3 (AI-V3/J
option required)
n03
→
1
b1-01
→
0
n03
→
2
b1-01
→
1 and H3-01
→
0
n03
→
3
b1-01
→
1 and H3-01
→
2
n03
→
4
b1-01
→
1 and H3-01
→
3
n03
→
6
b1-01
→
2 (SI-485/J)
option required)
When using A1 as frequency reference
input, make sure to set DIP switch S1
properly (voltage or current input).
Stop method selection
n04 0 b1-03 0
J7 J1000
n04
→
0 b1-03
→
0
n04
→
1 b1-03
→
1
Reverse run prohibit
selection
n05 0 b1-04 0
J7 J1000
n05
→
0 b1-04
→
0
n05
→
1 b1-04
→
1
Digital Operator STOP
key function
n06 0 o2-02 1
J7 J1000
n06
→
0 o2-02
→
1
n06
→
1 o2-02
→
0
Frequency reference in
local mode
n07 0 -
- - (no operator panel potentiometer)
Frequency reference
from operator ENTER
key selection
n08 0 o2-05 0
J7 J1000
n08
→
0 o2-05
→
0
n08
→
1 o2-05
→
1
Max. output frequency
n09
60.0 Hz
E1-04
60.0 Hz
Max. output voltage
n10
200 V *
E1-05
200 V *
* Values for a 400 V class drive are double.
Base frequency
n11 60.0Hz E1-06 60.0
Hz
Mid. output frequency
n12 1.5Hz E1-07 3.0
Hz
Mid. output voltage
n13
12 V *
E1-08
16.0 V *
* Values for a 400 V class drive are double.