2.4 Mounting
Requirements for UL compliance use
–
Use for power supply exclusively SELV/PELV power supplies.
–
The System SLIO must be installed and operated in a housing
according to IEC 61010-1 9.3.2 c).
2.4.1 Mounting CPU 01xC
There are locking lever at the top side of the CPU. For mounting and demounting these
locking lever are to be turned upwards until these engage. Place the CPU at the
mounting rail. The CPU is fixed to the mounting rail by pushing downward the locking
levers. The CPU is directly mounted at a mounting rail. Up to 64 modules may be
mounted. The electronic and power section supply are connected via the backplane bus.
Please consider here that the sum current of the electronic power supply does not
exceed the maximum value of 1A. By means of the power module 007-1AB10 the current
of the electronic power supply may be expanded accordingly.
1.
Mount the mounting rail! Please consider that a clearance from the middle of the
mounting rail of at least 80mm above and 60mm below, respectively 80mm by
deployment of shield bus carriers, exist.
Proceeding
VIPA System SLIO
Basics and mounting
Mounting > Mounting CPU 01xC
HB300 | CPU | 013-CCF0R00 | en | 19-30