![YASKAWA VIPA System SLIO Скачать руководство пользователя страница 198](http://html.mh-extra.com/html/yaskawa/vipa-system-slio/vipa-system-slio_manual_907132198.webp)
7.6.2 Steps of the OPC UA configuration
When using the Siemens TIA Portal, the
OPC UA
configuration happens by the following
steps:
1.
Create your project in the Siemens TIA Portal with the corresponding hardware con-
Chap. 13.3 ‘TIA Portal - Hardware configuration - CPU’ page 296
2.
Configure the corresponding Ethernet connection for PG/OP communication and
establish an online connection.
Chap. 13.4 ‘TIA Portal - Hardware configuration -
Ethernet PG/OP channel’ page 299
3.
Save translate and transfer your project.
Chap. 13.10 ‘TIA Portal - Project
4.
Call the external
OPC UA Configurator
from the Siemens TIA Portal. For this click
at
‘Devices & networks’
on the CPU of VIPA and select
‘Start device tool’
.
ð
A dialog window opens. Select
‘OPC UA Configurator’
and click [Start].
5.
Ignore the query
‘Set interface’
with [OK]
ð
The
OPC UA Configurator
is started.
6.
If not yet confirmed, you will now receive an access request in the TIA Portal.
Please note that due to the software the access request does not
appear in the foreground. To show the access request, you must
again bring the Siemens TIA Portal to the foreground. Once the
access has been selected, you must again bring the ‘OPC UA
Configurator’ to the foreground.
You have the following options for access:
n
‘No’
: Deny access - the
OPC UA Configurator
is not started.
n
‘Yes’
: Access is permitted once and the
OPC UA Configurator
is started.
n
‘Yes to all’
: Access is permitted and the
OPC UA Configurator
is started. At the
next call, the access request is no longer shown.
Allow access with
‘Yes’
respectively
‘Yes to all’
.
ð
NOTICE!
Data exchange between platforms of different vendors
If you allow access, you permit the exchange of data between
OPC UA Configurator
and your project data of the Siemens TIA
Portal.
–
Ensure that the necessary security guidelines are complied
with.
For the
OPC UA
configuration, the data is taken from the Siemens TIA Portal
project and listed in the table for the
OPC UA
configuration.
Please note that only the objects of the LD, FBD and IL lan-
guages can be transferred to the OPC UA Configurator.
7.
Configure the
OPC UA
server and the data for the
OPC UA
communication.
Steps of configuration
VIPA System SLIO
Deployment OPC UA
Usage in Siemens TIA Portal > Steps of the OPC UA configuration
HB300 | CPU | 013-CCF0R00 | en | 19-30
198