7.5.2 Steps of the OPC UA configuration
When using the Siemens SIMATIC Manager, the
OPC UA
configuration happens by the
following steps:
1.
Create your project in the Siemens SIMATIC Manager with the corresponding hard-
Chap. 4.5 ‘Hardware configuration - CPU’ page 69
2.
Configure the corresponding Ethernet connection for PG/OP communication and
establish an online connection.
Chap. 4.7 ‘Hardware configuration - Ethernet
3.
Save translate and transfer your project.
Chap. 4.10 ‘Project transfer’ page 90
4.
Call the external
OPC UA Configurator
from the Siemens SIMATIC Manager. For
this click in the hardware configurator on the CPU from VIPA and select
‘Start Device Tool
è
VIPA Framework
è
OPC UA Configurator’
.
5.
Confirm to start an external program with [YES].
NOTICE!
Data exchange between platforms of different vendors
If you allow access, you permit the exchange of data between
OPC UA Configurator
and your project data of the Siemens
SIMATIC Manager.
–
Ensure that the necessary security guidelines are complied
with.
ð
The
OPC UA Configurator
is started. For the
OPC UA
configuration, the data is
taken from the Siemens SIMATIC Manager project and listed in the table for the
OPC UA
configuration.
Please note that only the objects of the LD, FBD and IL lan-
guages can be transferred to the OPC UA Configurator.
6.
Configure the
OPC UA
server and the data for the
OPC UA
communication.
7.
In the
OPC UA Configurator
switch to the online dialog and transfer the
OPC UA
configuration. For communication the IP address data are taken from the Siemens
SIMATIC Manager project.
ð
The
OPC UA
configuration is now complete. For check you will find information
about your
OPC UA
configuration on the device web page at
‘OPC UA’
.
Chap. 4.11.1.1.1 ‘Tab: ‘OPC UA’ ’ page 97
7.6 Usage in Siemens TIA Portal
Siemens TIA Portal from version V15.0 and VIPA
SPEED7 Studio
from V1.8.6
n
The
OPC UA
configuration happens by the external
OPC UA Configurator
from VIPA.
n
The
OPC UA Configurator
is the
SPEED7 Studio
reduced to
OPC UA
functionality.
n
The
OPC UA Configurator
can be registered in the Siemens TIA Portal by means of
the
SPEED7 Tools Integration
.
n
The
OPC UA Configurator
is to be called from the Siemens TIA Portal after project
creation and online configuration.
n
The
OPC UA Configurator
automatically imports the data for the
OPC UA
configura-
tion from the project data of the Siemens TIA Portal.
n
The
OPC UA
configuration is transferred online from the
OPC UA Configurator
. For
the communication the
OPC UA Configurator
automatically uses the IP address data
of the Siemens TIA Portal project.
Steps of configuration
Precondition
VIPA System SLIO
Deployment OPC UA
Usage in Siemens TIA Portal