Operating parameters
Description
Assignment
Period
With the period you define the length of the output
sequence, which consists of pulse duration and pulse
pause.
Range of values:
Time base 1ms: 1 ... 87ms
Time base 0.1ms: 0.4 ... 87.0ms
50*
Minimum pulse duration
With the minimum pulse duration you can suppress short
output pulses and short pulse pauses. All pulses or
pauses, which are smaller than the minimum pulse dura-
tion, are suppressed. This allows you to filter very short
pulses (spikes), which can not be recognized by the
periphery.
Range of values:
Time base 1ms: 0 ... Period / 2 * 1ms
Time base 0.1ms: 2 ... Period / 2 * 0.1ms
2
*) This value can vary depending on the configuration tool and can be out of range. Values, which are out of range are invalid and must be adjusted accordingly!
5.8.5 Status indication
Digital output
LED
green
Description
DO +0.0
PWM 0 has "1" signal
PWM 0 has "0" signal
DO +0.1
PWM 1 has "1" signal
PWM 1 has "0" signal
VIPA System MICRO
Deployment I/O periphery
Pulse width modulation - PWM > Status indication