A
System specific event IDs
Chapter 4.19 ‘Diagnostic entries’ on page 85
Event ID
Description
0x115C
Vendor-specific interrupt (OB 57) at EtherCAT
OB: OB number
ZInfo1: Logical address of the slave that triggered the interrupt
ZInfo2: Interrupt type
0x00: Reserved
0x01: Diagnostic interrupt (incoming)
0x02: Hardware interrupt
0x03: Pull interrupt
0x04: Plug interrupt
0x05: Status interrupt
0x06: Update interrupt
0x07: Redundancy interrupt
0x08: Controlled by the supervisor
0x09: Enabled
0x0A: Wrong sub module plugged
0x0B: Restoration of the sub module
0x0C: Diagnostic interrupt (outgoing)
0x0D: Cross traffic connection message
0x0E: Neighbourhood change message
0x0F: Synchronisation message (bus)
0x10: Synchronisation message (device)
0x11: Network component message
0x12: Clock synchronisation message (bus)
0x1F: Pull interrupt module
ZInfo3: CoE error code
0xE003
Error on accessing the periphery
ZInfo1 : Transfer type
ZInfo2 : Periphery address
ZInfo3 : Slot
0xE004
Multiple configuration of a periphery address
ZInfo1 : Periphery address
ZInfo2 : Slot
0xE005
Internal error - Please contact the hotline!
0xE007
Configured in-/output bytes do not fit into periphery area
0xE008
Internal error - Please contact the hotline!
Event IDs
VIPA System MICRO
System specific event IDs
HB400 | CPU | M13-CCF0000 | en | 16-47
213
Содержание VIPA System MICRO M13-CCF0000
Страница 35: ...3 2 2 Interfaces VIPA System MICRO Hardware description Structure Interfaces HB400 CPU M13 CCF0000 en 16 47 35 ...
Страница 211: ...Appendix VIPA System MICRO Appendix HB400 CPU M13 CCF0000 en 16 47 211 ...
Страница 212: ...Content A System specific event IDs B Integrated blocks VIPA System MICRO Appendix HB400 CPU M13 CCF0000 en 16 47 212 ...