For isolated interfaces you have 5V (P5V) isolated at pin 6 and the corresponding ground
(M5V) at pin 5. With this isolated voltage, you can assign defined static voltage levels to
the signal lines and so ensure a low reflection level.
1
X1 PtP interface
2
Periphery
3
Send
4
Receive
*)
For line lengths >50m, you have to solder a terminating resistor of approx. 330
W
on
the receiver side for interference-free data traffic.
X1 PtP
TxD
Description
green flickers
Send activity
No send activity
7.4 Parametrization
7.4.1 FC/SFC 216 - SER_CFG - Parametrization PtP
The parametrization happens during runtime deploying the FC/SFC 216 (SER_CFG). You
have to store the parameters for STX/ETX, 3964R, USS and Modbus in a DB.
RS422 cabling with
defined static voltage
levels
Status indication
VIPA System MICRO
Option: PtP communication
Parametrization > FC/SFC 216 - SER_CFG - Parametrization PtP
HB400 | CPU | M13-CCF0000 | en | 16-47
160
Содержание VIPA System MICRO M13-CCF0000
Страница 35: ...3 2 2 Interfaces VIPA System MICRO Hardware description Structure Interfaces HB400 CPU M13 CCF0000 en 16 47 35 ...
Страница 211: ...Appendix VIPA System MICRO Appendix HB400 CPU M13 CCF0000 en 16 47 211 ...