Wiring
Most peripheral modules are equipped with a 10pole or a 18pole connector.
This connector provides the electrical interface for the signaling and supply
lines of the modules.
The modules carry spring-clip connectors for interconnections and wiring.
The spring-clip connector technology simplifies the wiring requirements for
signaling and power cables.
In contrast to screw terminal connections, spring-clip wiring is vibration
proof. The assignment of the terminals is contained in the description of the
respective modules.
You may connect conductors with a diameter from 0.08mm
2
up to 2.5mm
2
(max. 1.5mm
2
for 18pole connectors).
The following figure shows a module with a 10pole connector.
1
2
3
4
5
6
7
8
9
10
1
2
3
3 4 5
1
1
1
2
3
4
5
6
7
8
9
10
2
[1]
[2]
[3]
[4]
[5]
Locking lever
Pin no. at the module
Pin no. at the connector
Wiring port
Opening for screwdriver
Note!
The spring-clip is destroyed if you push the screwdriver into the wire port!
Make sure that you only insert the screwdriver into the square hole of the
connector!
Overview
Содержание VIPA System 200V
Страница 1: ...VIPA System 200V CPU Manual HB97E_CPU RE_21x 2BS03 Rev 15 16 April 2015 ...
Страница 4: ...Contents Manual VIPA System 200V ii HB97E CPU RE_21x 2BS03 Rev 15 16 ...
Страница 8: ...Safety information Manual VIPA System 200V 4 HB97E CPU RE_21x 2BS03 Rev 15 16 ...
Страница 66: ...Chapter 3 Deployment CPU 21x 2BS03 Manual VIPA System 200V 3 28 HB97E CPU RE_21x 2BS03 Rev 15 16 ...