2.13 Installation guidelines
The installation guidelines contain information about the interference free deployment of a
PLC system. There is the description of the ways, interference may occur in your PLC,
how you can make sure the electromagnetic compatibility (EMC), and how you manage
the isolation.
Electromagnetic compatibility (EMC) means the ability of an electrical device, to function
error free in an electromagnetic environment without being interfered respectively without
interfering the environment.
The VIPA components are developed for the deployment in industrial environments and
meets high demands on the EMC. Nevertheless you should project an EMC planning
before installing the components and take conceivable interference causes into account.
Electromagnetic interferences may interfere your control via different ways:
n
Electromagnetic fields (RF coupling)
n
Magnetic fields with power frequency
n
Bus system
n
Power supply
n
Protected earth conductor
Depending on the spreading medium (lead bound or lead free) and the distance to the
interference cause, interferences to your control occur by means of different coupling
mechanisms.
There are:
n
galvanic coupling
n
capacitive coupling
n
inductive coupling
n
radiant coupling
In the most times it is enough to take care of some elementary rules to guarantee the
EMC. Please regard the following basic rules when installing your PLC.
n
Take care of a correct area-wide grounding of the inactive metal parts when installing
your components.
–
Install a central connection between the ground and the protected earth conductor
system.
–
Connect all inactive metal extensive and impedance-low.
–
Please try not to use aluminium parts. Aluminium is easily oxidizing and is there-
fore less suitable for grounding.
n
When cabling, take care of the correct line routing.
–
Organize your cabling in line groups (high voltage, current supply, signal and data
lines).
–
Always lay your high voltage lines and signal respectively data lines in separate
channels or bundles.
–
Route the signal and data lines as near as possible beside ground areas (e.g.
suspension bars, metal rails, tin cabinet).
General
What does EMC mean?
Possible interference
causes
Basic rules for EMC
VIPA System SLIO
Basics and mounting
Installation guidelines
HB300 | FM | 050-1BB30 | en | 20-40