background image

1 Preface and General Safety

YASKAWA

TOEPYAISPC03 UL Type 1 Kit for Single Phase Converter Installation Manual

5

General Safety

General Precautions

The diagrams in this manual may be indicated without covers or safety shields to show details. Replace the covers or shields before operating the SPC and run the SPC according to
the instructions described in this manual.

Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to which this manual is applicable.

The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual.

When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest Yaskawa sales office and provide the manual number shown on
the front cover.

If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or the nearest Yaskawa sales office.

WARNING

Read and understand this manual before installing, operating or servicing this converter. The converter must be

installed according to this manual and local codes. The following conventions are used to indicate safety messages in this manual.
Failure to heed these messages could result in serious or fatal injury or damage to the products or to related equipment and
systems.

DANGER

Indicates a hazardous situation, which, if not avoided, WILL result in death or serious injury.

WARNING

Indicates a hazardous situation, which, if not avoided, COULD result in death or serious injury.

CAUTION

Indicates a hazardous situation, which, if not avoided, COULD result in MINOR OR MODERATE injury.

NOTICE

Indicates a PROPERTY DAMAGE MESSAGE.

Safety Messages

DANGER

Heed the safety messages in this manual. The operating company is responsible for any injuries or equipment

damage resulting from failure to heed the safety messages in this manual. Failure to comply will result in death or serious injury.

DANGER

Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in

death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after
the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent
electric shock, wait for at least the time specified on the warning label, once all indicators are OFF, measure for unsafe voltages to
confirm the converter is safe prior to servicing. Failure to comply will result in death or serious injury.

WARNING

Sudden Movement Hazard. System may start unexpectedly when the unit is energized, resulting in death or

serious injury. Clear all personnel from the converter, drive, motor, and machine area before energizing. Secure covers, couplings,
shaft keys, and machine loads before energizing.

WARNING

Electrical Shock Hazard. Do not attempt to modify or alter the converter in any way not explained in this manual.

Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. Failure to
comply could result in death or serious injury.

WARNING

Electrical Shock Hazard. Do not allow unqualified personnel to use equipment. Installation, maintenance,

inspection, and service must be performed only by authorized personnel familiar with installation, adjustment and maintenance of
AC converters. Failure to comply could result in death or serious injury.

WARNING

Electrical Shock Hazard. Do not remove covers or touch circuit boards while the power is on. Failure to comply

could result in death or serious injury.

WARNING

Electrical Shock Hazard. Make sure the protective earthing conductor complies with technical standards and local

safety regulations. Because the leakage current exceeds 3.5 mA, IEC/EN/UL 61800-5-1 states that either the power supply must be
automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing conductor with a
cross-section of at least 10 mm

2

(Cu) or 16 mm

2

(Al) must be used. Failure to comply could result in death or serious injury.

WARNING

Electrical Shock Hazard. Use appropriate equipment for Ground Fault Circuit Interrupters (GFCIs). The converter

can cause a residual current with a DC component in the protective earthing conductor. Use a type B GFCI according to IEC/EN
60755, where a residual current operated protective or monitoring device is used for protection in case of direct or indirect contact.
Failure to comply could result in death or serious injury.

WARNING

Fire Hazard. Do not use an improper voltage source. Verify that the rated voltage of the converter matches the

voltage of the incoming power supply before applying power. Failure to comply could result in death or serious injury by fire.

WARNING

Fire Hazard. Install adequate branch circuit protection according to applicable local codes and this Installation

Manual. The device is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 240 Vac
maximum (200 V class) and 480 Vac maximum (400 V class), when protected by branch circuit protection devices specified in this
document. Failure to comply could result in death or serious injury by fire.

CAUTION

Crush Hazard. Do not carry the converter by the front cover. Failure to comply may result in minor or moderate

injury from the main body of the converter falling.

Содержание UUX001686

Страница 1: ...rive Option Installation Manual Type UUX001686 UUX001687 UUX001703 Models 200 V class 20 to 60 HP 400 V class 30 to 125 HP To properly use the product read this manual thoroughly and retain for easy r...

Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAISPC03 UL Type 1 Kit for Single Phase Converter Installation Manual...

Страница 3: ...n Manual 3 Table of Contents 1 Preface and General Safety 4 General Description 4 Option Package Contents 4 Applicable Documentation 4 General Safety 5 2 Kit Installation 7 Section Safety 7 Installati...

Страница 4: ...crew 4 ea USP04765 1 Applicable Documentation Document Description YASKAWA AC Drive Option UL Type 1 Kit for Single Phase Converter Installation Manual Read this manual before you install this option...

Страница 5: ...ING Sudden Movement Hazard System may start unexpectedly when the unit is energized resulting in death or serious injury Clear all personnel from the converter drive motor and machine area before ener...

Страница 6: ...e equipment if a fuse is blown or a Ground Fault Circuit Interrupter GFCI is tripped Repair the cause of the problem prior to re energizing the equipment Check the wiring and the selection of the peri...

Страница 7: ...ing the converter inside an enclosed panel or cabinet When multiple drives are placed inside the same enclosure panel install proper cooling to ensure air entering the enclosure does not exceed 40 C F...

Страница 8: ...xterior and Mounting Dimensions Table 2 1 UL Type 1 Kit Mounting Dimensions SPC Model Kit Number Knockout Dimension Figure Dimensions mm in W H D D1 H1 H2 2015 2022 4022 4030 UUX001686 Figure 2 2 256...

Страница 9: ...2 50 1 97 44 1 73 35 1 38 Figure 2 3 Frame 2 Conduit Knockout Dimensions Table 2 3 Frame 2 Conduit Knockout Dimensions Dimensions mm in D D1 W W1 W2 W3 W4 W5 d2 d3 d4 d5 48 1 89 157 6 19 94 5 3 72 68...

Страница 10: ...in D D1 D2 W W1 W2 W3 d3 d4 d5 79 3 11 155 6 09 106 4 17 75 2 95 65 2 56 22 3 0 88 90 3 54 50 1 97 35 1 38 62 2 44 Figure 2 5 Frame 3B Conduit Knockout Dimensions Table 2 5 Frame 3B Conduit Knockout D...

Страница 11: ...ded M4 x 10 captive pan head screws to attach the top cover Tighten the screws to a tightening torque of 0 98 to 1 33 N m 8 67 to 11 77 in lb Figure 2 6 Attach the Top Cover 4 Remove the two bottom li...

Страница 12: ...67 to 11 77 in lb Note Kit UUX001783 ships with two heatsink covers Use the information in Table 2 6 to select the correct cover The part number is stamped on the part for identification You can disc...

Страница 13: ...the screws to a tightening torque of 3 92 to 4 90 N m 34 69 to 43 37 in lb Figure 2 9 Attach the Bottom Housing 7 Remove the necessary conduit knockouts To remove a conduit knockout insert the tip of...

Страница 14: ...to the manual packaged with the SPC for wiring instructions Figure 2 11 Wire the SPC 9 Use the provided M4 x 10 truss head screws to attach the bottom cover Tighten the screws to a tightening torque o...

Страница 15: ...ion YASKAWA TOEPYAISPC03 UL Type 1 Kit for Single Phase Converter Installation Manual 15 10 The kit installation is complete and the SPC is now enclosed in a UL Type 1 enclosure Figure 2 13 Installati...

Страница 16: ...16 YASKAWA TOEPYAISPC03 UL Type 1 Kit for Single Phase Converter Installation Manual Revision History Date of Publication Revision Number Section Revised Content February 2019 First Edition...

Страница 17: ...YASKAWA TOEPYAISPC03 UL Type 1 Kit for Single Phase Converter Installation Manual 17...

Страница 18: ...reign Trade Regulations Therefore be sure to follow all procedures and submit all relevant documentation according to any and all rules regulations and laws that may apply Specifications are subject t...

Отзывы: