![YASKAWA U1000 Series Скачать руководство пользователя страница 523](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114523.webp)
B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
523
t
B
U1-04
(43H)
Control Method
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
No signal output
available
–
–
U1-05
(44H)
Motor Speed
Displays the motor speed feedback. Display units are determined by o1-03.
10 V: Max Frequency
(-10 to +10 V)
0.01 Hz
–
U1-06
(45H)
Output Voltage Reference
Displays the output voltage.
10 V: 200 Vrms
0.1 Vac
–
U1-07
(46H)
Control Circuit Voltage
Displays the control circuit voltage.
10 V: 400 V
1 Vdc
–
U1-08
(47H)
Output Power
Displays the output power (this value is calculated internally).
10 V:
(-10 to +10 V)
–
U1-09
(48H)
Torque Reference
Monitors the internal torque reference.
10 V: Motor rated
torque
(-10 to +10 V)
0.1%
–
U1-10
(49H)
Input Terminal Status
Displays the input terminal status.
No signal output
available
–
–
No. (Addr.)
Name
Description
Analog Output
Level
Unit
Page
All Modes
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
All Modes
All Modes
All Modes
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
All Modes
U1 - 10=
0 0 0 0 0 0 0 0
Digital input 1
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
Digital input 8
(terminal S8 enabled)
1
1
1
1
1
1
1
1
SIEP_C710636_02B_1_0.book 523 ページ 2015年11月25日 水曜日 午後4時56分