B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
503
t
B
■
H3: Multi-Function Analog Inputs
90 to 92
DriveWorksEZ Digital Outputs 1 to 3
Reserved for DWEZ digital output functions.
100 to 192
Function 0 to 92 with Inverse Output
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1
to reverse the output signal of that specific function.
No.(Addr.)
Name
Description
Setting
Page
H3-01
(410H)
Terminal A1 Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min: 0
Max: 1
H3-02
(434H)
Terminal A1 Function Selection
Sets the function of terminal A1.
Default: 0
Min: 0
Max: 32
H3-03
(411H)
Terminal A1 Gain Setting
Sets the level of the input value selected in H3-02 when 10 V is input at terminal A1.
Default: 100.0%
Min: -999.9%
Max: 999.9%
H3-04
(412H)
Terminal A1 Bias Setting
Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1.
Default: 0.0%
Min: -999.9%
Max: 999.9%
H3-05
(413H)
Terminal A3 Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min: 0
Max: 1
H3-06
(414H)
Terminal A3 Function Selection
Sets the function of terminal A3.
Default: 2
Min: 0
Max: 32
H3-07
(415H)
Terminal A3 Gain Setting
Sets the level of the input value selected in H3-06 when 10 V is input at terminal A3.
Default: 100.0%
Min: -999.9%
Max: 999.9%
H3-08
(416H)
Terminal A3 Bias Setting
Sets the level of the input value selected in H3-06 when 0 V is input at terminal A3.
Default: 0.0%
Min: -999.9%
Max: 999.9%
H3-09
(417H)
Terminal A2 Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note:
Use DIP switch S1 to set input terminal A2 for a current or a voltage input signal.
Default: 2
Min: 0
Max: 3
H3-10
(418H)
Terminal A2 Function Selection
Sets the function of terminal A2.
Default: 0
Min: 0
Max: 32
H3-11
(419H)
Terminal A2 Gain Setting
Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input at terminal A2.
Default: 100.0%
Min: -999.9%
Max: 999.9%
H3-12
(41AH)
Terminal A2 Bias Setting
Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is input at terminal A2.
Default: 0.0%
Min: -999.9%
Max: 999.9%
H3-13
(41BH)
Analog Input Filter Time Constant
Sets a primary delay filter time constant for terminals A1, A2, and A3. Used for noise filtering.
Default: 0.03 s
Min: 0.00 s
Max: 2.00 s
H3-14
(41CH)
Analog Input Terminal Enable
Selection
Determines which of the analog input terminals will be enabled or disabled when a digital input
programmed for “Analog input enable” (H1-
= C) is activated. The terminals other than the
one set as the target are not influenced by input signals.
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
Default: 7
Min: 1
Max: 7
H3-16
(2F0H)
Terminal A1 Offset
Adds an offset when the analog signal to terminal A1 is at 0 V.
Default: 0
Min: -500
Max: 500
H3-17
(2F1H)
Terminal A2 Offset
Adds an offset when the analog signal to terminal A2 is at 0 V.
Default: 0
Min: -500
Max: 500
H2 Multi-Function Digital Output Settings
H2-
Setting
Function
Description
Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
SIEP_C710636_02B_1_0.book 503 ページ 2015年11月25日 水曜日 午後4時56分