6.6 Operator Programming Errors
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
375
T
rou
bl
es
hoot
ing
6
Digital Operator Display
Error Name
oPE13
Pulse Monitor Selection Error
Incorrect setting of monitor selection for pulse train (H6-06).
Cause
Possible Solutions
Scaling for the pulse train monitor is set to 0 (H6-07 = 0) while H6-06 is not set to 101, 102,
105, or 116.
Change scaling for the pulse train monitor or set H6-06 to 101, 102, 105, or 116.
Digital Operator Display
Error Name
oPE15
Torque Control Setting Error
Parameters settings that are not allowed in combination with Torque Control have been set.
Cause
Possible Solutions
Torque Control in enabled (d5-01 = 1) while the Speed/Torque Control switch function is
assigned to a digital input (H1-
= 71).
Correct the parameter settings.
Either Torque Control is enabled by d5-01 = 1, the or Speed/Torque Control switch is assigned
to a digital input H1-
= 71, while at the same time:
• Feed Forward is enabled (n5-01 = 1) or
• Droop Control is enabled (b7-01
≠
0)
Digital Operator Display
Error Name
oPE16
Energy Savings Constants Error
Cause
Possible Solutions
In AOLV/PM the automatically calculated energy saving coefficients are out of the allowable
range.
Check and correct the motor data in E5 parameters.
Digital Operator Display
Error Name
oPE18
Online Tuning Parameter Setting Error
Parameters that control Online Tuning are not set correctly.
Cause
Possible Solutions
One of the following setting errors has occurred while Online Tuning is enabled in OLV
(A1-02 = 2):
• E2-02 has been set below 30% of the original default value
• E2-06 has been set below 50% of the original default value
• E2-03 = 0
Make sure E2-02, E2-03, and E2-06 are set the correct values.
Digital Operator Display
Error Name
oPE20
PG-F3 Setting Error
The encoder signal frequency is too high.
Cause
Possible Solutions
With the entered encoder resolution (F1-01), maximum output frequency (E1-04), and motor
pole number (E5-04,) the calculation encoder signal frequency exceeds 50 kHz (with PG-F3
option).
• Set F1-01 to the correct encoder resolution.
• Reduce the maximum output frequency of the drive in parameter E1-04 so the encoder
signal frequency at maximum speed is lower than 50 kHz.
Digital Operator Display
Error Name
oPE30
Incorrect Input Voltage Adjustment
The input voltage offset adjustment has not been performed.
Cause
Possible Solutions
• The setting of o2-04 (Drive Model Selection) changed.
• EEPROM failed for the input voltage offset.
For information on clearing the fault, contact Yaskawa or your nearest sales representative.