6.4 Fault Detection
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
365
T
rou
bl
es
hoot
ing
6
Digital Operator Display
Fault Name
Uv1
Control Circuit Undervoltage Fault
One of the following conditions occurred:
• For 200 V class: approximately 175 V
• For 400 V class: approximately 350 V
Cause
Possible Solution
Input power phase loss.
• The main circuit drive input power is wired incorrectly.
• Correct the wiring.
One of the drive input power wiring terminals is loose.
• Ensure there are no loose terminals.
• Apply the tightening torque specified in this manual to fasten the terminals.
Refer to Main Circuit Wire Gauges and
There is a problem with the voltage from the drive input
power.
• Check the voltage.
• Correct the voltage to be within the range listed in drive input power specifications.
• If there is no problem with the power supply to the main circuit, check for problems with the main circuit magnetic contactor.
The power has been interrupted.
Correct the drive input power.
The capacitors are worn.
• Check the maintenance time for the capacitors (U4-05).
• Replace the entire drive if U4-05 exceeds 90%. Contact Yaskawa or your nearest sales representative.
The relay or contactor on the soft-charge bypass circuit
is damaged.
• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace the entire drive. Contact Yaskawa or your nearest sales representative.
• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace the entire drive if U4-06 exceeds 90%. Contact Yaskawa or your nearest sales representative.
Digital Operator Display
Fault Name
Uv2
Control Power Supply Voltage Fault
Voltage is too low for the control drive input power.
Cause
Possible Solution
Control power supply wiring is damaged.
• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace the entire drive or the control power supply.
Internal circuitry is damaged.
• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace the entire drive. Contact Yaskawa or your nearest sales representative.
Digital Operator Display
Fault Name
Uv3
Undervoltage 3 (Soft-Charge Bypass Circuit Fault)
The soft-charge bypass circuit has failed.
Cause
Possible Solution
The relay or contactor on the soft-charge bypass circuit
is damaged.
• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace the entire drive. Contact Yaskawa or your nearest sales representative.
• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace the entire drive if U4-06 exceeds 90%. Contact Yaskawa or your nearest sales representative.
<1> Displayed as CPF00 or CPF20 when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the
display will show CPF01 or CPF21.
<2> This function prevents continuous operation in reverse when using high frequency injection (n8-57 = 1) in the Advanced Open Loop Vector
Control mode for PM motors (A1-02 = 6) with a motor for which no motor code has been entered (it does not simply prevent reverse
operation). Set L8-93, L8-94, and L8-95 to low values within range of erroneous detection to quickly detect undesirable reverse operation.
SIEP_C710636_02B_1_0.book 365 ページ 2015年11月25日 水曜日 午後4時56分