5.10 o: Operator Related Settings
334
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
Setting 0: ENTER key required
Every time the frequency reference is changed using the digital operator, the ENTER key must be pressed for the drive to
accept the change.
Setting 1: ENTER key not required
The output frequency changes immediately when the reference is changed by the up or down arrow keys on the digital
operator. The ENTER key does not need to be pressed. The frequency reference (Fref) is saved to memory after
remaining unchanged for 5 seconds.
■
o2-06: Operation Selection when Digital Operator is Disconnected
Determines if the drive will stop when the remote control extension cable of the digital operator is removed in LOCAL
mode or when b1-02 or b1-16 is set to 0. When the operator is reconnected, the display will indicate that it was
disconnected.
Setting 0: Continue operation
The operation is continued.
Setting 1: Trigger a fault
The operation is stopped and an “oPr” fault is triggered. The motor coasts to stop.
■
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up and the Run command is given from the
digital operator.
Note:
This parameter is effective only when the Run command is set to be given from the digital operator (b1-02, b1-16 = 0).
Setting 0: Forward
Setting 1: Reverse
◆
o3: Copy Function
These parameters control the digital operator’s Copy function. The Copy function lets the user store all parameter
settings into the memory of the digital operator, and easily transfer those settings to other drives (requires that the other
drives be the same model, capacity, and have the same control mode setting).
Refer to Copy Function Related Displays
for a description of errors and displays.
■
o3-01 Copy Function Selection
Setting o3-01 will instruct the drive to Read, Write, or Verify parameters settings.
Setting 0: Copy Select (no function)
Setting 1: INV --> OP READ
All parameters are copied from the drive to the digital operator.
Note:
Set o3-02 to 1 to unlock copy protection.
Setting 2: OP --> INV WRITE
All parameters are copied from the digital operator to the drive.
Setting 3: OP<-->INV VERIFY
Parameters in the drive are compared with the parameter settings saved on the digital operator to see if they match.
No.
Name
Setting Range
Default
o2-06
Operation Selection when Digital Operator is Disconnected
0 or 1
0
No.
Name
Setting Range
Default
o2-07
Motor Direction at Power Up when Using Operator
0 or 1
0
No.
Name
Setting Range
Default
o3-01
Copy Function Selection
0 to 3
0
SIEP_C710636_02B_1_0.book 334 ページ 2015年11月25日 水曜日 午後4時56分