5.6 F: Option Settings
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
261
5
■
F2-02, F2-03: Analog Input Option Card Gain, Bias
Parameter F2-02 sets the gain and parameter F2-03 sets the bias for the AI-A3 input signal when the card is used in the
combined input signals mode (F2-01 = 1). Both gain and bias are set as a percentage of the maximum output frequency.
Note:
Enabled only when F2-01 = 1.
◆
F3: Digital Input Card Settings
These parameters set up the drive for operation with the option card DI-A3. This section describes parameters that
govern operation with a digital input option card. Refer to the instruction manual packaged with the option card for
specific details on installation, wiring, input signal level selection, and parameter setup.
■
F3-01: Digital Input Option Card Input Selection
Determines the type of input for digital option card DI-A3 when o1-03 is set to 0 or 1.
Setting 0: BCD, 1% units
Setting 1: BCD, 0.1% units
Setting 2: BCD, 0.01% units
Setting 3: BCD, 1 Hz units
Setting 4: BCD, 0.1 Hz units
Setting 5: BCD, 0.01 Hz units
Setting 6: BCD, special setting (5 digit input), 0.02 Hz units
Setting 7: Binary
The unit and the setting range are determined by F3-03.
F3-03 = 0: 255/100% (-255 to +255)
F3-03 = 1: 4095/100% (-4095 to +4095)
F3-03 = 2: 30000/100% (-33000 to +33000)
Note:
BCD input when o1-03 = 2 or 3. Units are determined by o1-03.
■
F3-03: Digital Input Option DI-A3 Data Length Selection
Determines the number of bits for the option card input that sets the frequency reference.
Setting 0: 8 bit
Setting 1: 12 bit
Setting 2: 16 bit
◆
F4: Analog Monitor Card Settings
These parameters set up the drive for operation with the analog output option card AO-A3. This section describes
parameters that govern operation with an analog output option card. Refer to the instruction manual packaged with the
option card for specific details on installation, wiring, input signal level selection, and parameter setup.
■
F4-01, F4-03: Terminal V1, V2 Monitor Selection
Selects the data to output from analog terminal V1. Enter the final three digits of U
-
to determine which monitor
data is output from the option card. Some monitors are only available in certain control modes.
No.
Parameter Name
Setting Range
Default
F2-02
Analog Input Option Card Gain
-999.9 to 999.9%
100.0%
F2-03
Analog Input Option Card Bias
-999.9 to 999.9%
0.0%
No.
Parameter Name
Setting Range
Default
F3-01
Digital Input Option Card Input Selection
0 to 7
0
No.
Parameter Name
Setting Range
Default
F3-03
Digital Input Option DI-A3 Data Length Selection
0 to 2
2
No.
Parameter Name
Setting Range
Default
F4-01
Terminal V1 Monitor Selection
000 to 999
102