4.5 Powering Up the Drive
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
147
St
ar
t-
Up Pr
ogr
ammi
ng
&
O
p
er
at
io
n
4
4.5 Powering Up the Drive
◆
Powering Up the Drive and Operation Status Display
■
Powering Up the Drive
Review the following checklist before turning the power on.
■
Status Display
When the power supply to the drive is turned on, the digital operator lights will appear as follows:
Item to Check
Description
Power supply voltage
Ensure the power supply voltage is correct:
200 V class: 3-phase 200 to 240 Vac 50/60 Hz
400 V class: CIMR-U
4A
, CIMR-U
4P
: 3-phase 380 to 500 Vac 50/60 Hz
400 V class: CIMR-U
4E
, CIMR-U
4W
: 3-phase 380 to 480 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3).
Check for proper grounding of drive and motor.
Use a power supply with a capacity that is equal to or greater than the unit capacity.
Drive output terminals and motor
terminals
Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W.
Control circuit terminals
Check control circuit terminal connections.
Drive control terminal status
Open all control circuit terminals (off).
Status of the load and connected
machinery
Decouple the motor from the load.
Status
Display
Description
Normal Operation
The data display area displays the frequency reference. Rdy is displayed.
Fault
External fault (example)
Data displayed varies by the type of fault. Refer to
Fault Displays, Causes, and Possible Solutions on page 354
for more information and possible solution.
is displayed.
DIGITAL OPERATOR JVOP-180
ALM
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (AI)
Rdy
RSEQ
RREF
FWD
JOG
DIGITAL OPERATOR JVOP-180
ALM
- MODE -
EF3
Ext Fault S3
DRV
FWD
RESET
ALM