![YASKAWA U1000 Series Скачать руководство пользователя страница 140](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114140.webp)
4.3 The Drive and Programming Modes
140
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
◆
Verifying Parameter Changes: Verify Menu
The Verify Menu lists edited parameters from the Programming Mode or as a result of Auto-Tuning. It helps determine
which settings have been changed, and is particularly useful when replacing a drive. If no settings have been changed, the
Verify Menu will read “None”. The Verify Menu also allows users to quickly access and re-edit any parameters settings
that have been changed.
Note:
The Verify Menu will not display parameters from the A1 group (except for A1-02) and E5-01 even if those parameters have
been changed from their default settings.
The following example is a continuation of the steps above. Here, parameter C1-02 is accessed using the Verify Menu,
and is changed again from 10.0 s to 20.0 s.
To check the list of edited parameters:
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
2.
Press
or
until the display shows the top of the Verify Menu.
3.
Press
to enter the list of parameters that have been edited from their original default settings.
If parameters other than C1-02 have been changed, use the
or
key to scroll until C1-02 appears.
4.
Press the
key.
Press
,
,
,
, and
to change the setting value.
5.
Press
and the drive will confirm the change.
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (AI)
Rdy
RSEQ
RREF
FWD
JOG
- MODE -
PRG
Modified Consts
HELP
DATA
FWD
Modified
X Parameters
C1-02
= 20.0sec
(0.0~6000.0)
“10.0sec”
FWD
- VERIFY - PRG
Accel Time 1
Rdy
Home
DATA
F1
F2
FWD
C1-01=
0
020.0sec
(0.0~6000.0)
“10.0sec”
- VERIFY - PRG
Accel Time 1
Rdy
←
→
Entry Accepted
SIEP_C710636_02B_1_0.book 140 ページ 2015年11月25日 水曜日 午後4時56分