3.14 24 V Control Power Supply Unit Wiring
3
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
123
3.14 24 V Control Power Supply Unit Wiring
◆
24 V Control Power Supply Unit
The 24 V Control Power Supply Unit maintains drive control circuit power in the event of a main power outage. As long
as the control circuit has power, network communications and I/O data remain operational. The unit provides external
power to the control circuit only, and does not provide power to the main circuit of the drive.
It is possible to read fault and parameter data in the drive via the operator or network communications when the drive
switches to the unit as a back-up power supply.
Note:
Parameter settings cannot be changed without drive main circuit power regardless of whether the control circuit has enough
power to operate.Parameter settings cannot be changed without drive main circuit power regardless of whether the control circuit
has enough power to operate.
■
24 V Control Power Supply Unit Location
Figure 3.73
Figure 3.72 24 V Control Power Supply Unit Location
(Models 2P0028, 2W0028, 4P0011 to 4P0034, and 4W0011 to 4W0034)
Figure 3.74
Figure 3.73 24 V Control Power Supply Unit Location
(Models 2P0042 to 2P0081, 2W0042 to 2W0081, 4P0040 to 4P0077, and 4W0040 to 4W0077)
Power Supply
Terminal Block
TB1
Power Supply
Terminal Block
TB1