A
B
A – Main circuit terminal
B – Terminals p1 and n1
Figure 3.24 Protective Cover Example (Drive Model 2
o
0104)
u
Main Circuit Wire Gauges and Tightening Torque
Use the tables in this section to select the appropriate wires and crimp terminals.
Gauges listed in the tables are for use in the United States.
Note:
Wire gauge recommendations based on drive continuous current ratings (ND) using 75 °C (167 °F) 600 Vac vinyl-sheathed wire assuming
ambient temperature within 40 °C (104 °F) and wiring distance less than 100 m.
Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater
than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to calculate
the amount of voltage drop:
Line drop voltage (V) = 3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10
-3
Refer to UL Standards Compliance on page 412
for information on UL compliance.
The wire gauges listed in the following tables are Yaskawa recommendations. Refer to local codes for proper wire gauge
selections.
n
Three-Phase 200 V Class Drives
Table 3.3 Drive Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
Drive
Model
Terminal
For USA and Canada
For South America
Screw
Size
Tightening
Torque
N·m (lb.in.)
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
2
o
0028
R/L1, S/L2, T/L3
10
(8)
6 to 10
(10 to 8)
4
(12)
2.5 to 10
(14 to 8)
M5
2.3 to 2.7
(20.4 to 23.9)
U/T1, V/T2, W/T3
10
(8)
6 to 10
(10 to 8)
4
(12)
2.5 to 10
(14 to 8)
M5
10
(8)
6 to 16
(10 to 6)
6
(10)
6 to 16
(10 to 5)
M6
3.9 to 4.9
(34.7 to 43.4)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1 to 1.4
(8.9 to 12.4)
2
o
0042
R/L1, S/L2, T/L3
16
(6)
10 to 25
(8 to 3)
10
(8)
6 to 25
(10 to 3)
M6
4 to 6
(35.4 to 53.1)
U/T1, V/T2, W/T3
16
(6)
10 to 25
(8 to 3)
10
(8)
6 to 25
(10 to 3)
M6
10
(8)
6 to 25
(10 to 3)
10
(8)
6 to 25
(10 to 3)
M8
8.8 to 10.8
(78.1 to 95.5)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1 to 1.4
(8.9 to 12.4)
3.8 Main Circuit Wiring
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
67
3