A.4 Drive Derating Data
The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.
u
Rated Current Depending on Carrier Frequency
The table below shows the drive output current depending on the carrier frequency settings.
Use the data in the following tables to linearly calculate output current values for carrier frequencies not listed.
Table A.7 Three-Phase 200 V Class Carrier Frequency and Current Derating
Drive Model
Setting Range
Rated Current [A]
4 kHz
6 kHz
8 kHz
10 kHz
2
o
0028
4 to 10 kHz
28
25
22
20
2
o
0042
4 to 10 kHz
42
38
34
29
2
o
0054
4 to 10 kHz
54
49
43
38
2
o
0068
4 to 10 kHz
68
61
54
48
2
o
0081
4 to 10 kHz
81
73
65
57
2
o
0104
4 to 8 kHz
104
94
83
—
2
o
0130
4 to 8 kHz
130
117
104
—
2
o
0154
4 to 6 kHz
154
139
—
—
2
o
0192
4 to 6 kHz
192
173
—
—
2
o
0248
4 kHz
248
—
—
—
Table A.8 Three-Phase 400 V Class Carrier Frequency and Current Derating
Drive Model
Setting Range
Rated Current [A]
4 kHz
6 kHz
8 kHz
10 kHz
4
o
0011
4 to 10 kHz
11
9.9
8.8
7.7
4
o
0014
4 to 10 kHz
14
13
11
9.8
4
o
0021
4 to 10 kHz
21
19
17
15
4
o
0027
4 to 10 kHz
27
24
22
19
4
o
0034
4 to 10 kHz
34
31
27
24
4
o
0040
4 to 10 kHz
40
36
32
28
4
o
0052
4 to 10 kHz
52
47
42
36
4
o
0065
4 to 10 kHz
65
59
52
46
4
o
0077
4 to 10 kHz
77
69
62
54
4
o
0096
4 to 8 kHz
96
86
77
—
4
o
0124
4 to 8 kHz
124
112
99
—
4
o
0156
4 to 6 kHz
156
140
—
—
4
o
0180
4 to 6 kHz
180
162
—
—
4
o
0216
4 kHz
216
—
—
—
4
o
0240
4 kHz
240
—
—
—
4
o
0302
4 kHz
302
—
—
—
4
o
0361
4 kHz
361
—
—
—
4
o
0414
4 kHz
414
—
—
—
A.4 Drive Derating Data
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
271
A
Specifications