A.3 Drive Watt Loss Data
u
Drive Models 2
o
0028 to 2
o
0248
Table A.5 Watt Loss 200 V Class Three-Phase Models
Drive Model
Rated Amps (A)
Heatsink Loss (W)
Interior Unit Loss (W)
Total Loss (W)
2
o
0028
28
659
103
762
2
o
0042
42
854
168
1022
2
o
0054
54
1037
195
1232
2
o
0068
68
1295
225
1520
2
o
0081
81
1420
238
1658
2
o
0104
104
1696
282
1978
2
o
0130
130
2157
341
2498
2
o
0154
154
2441
366
2807
2
o
0192
192
3064
447
3511
2
o
0248
248
3785
578
4363
u
Drive Models 4
o
0011 to 4
o
0414
Table A.6 Watt Loss 400 V Class Three-Phase Models
Drive Model
Rated Amps (A)
Heatsink Loss (W)
Interior Unit Loss (W)
Total Loss (W)
4
o
0011
11
452
80
532
4
o
0014
14
459
79
538
4
o
0021
21
641
105
746
4
o
0027
27
675
106
781
4
o
0034
34
798
124
922
4
o
0040
40
877
174
1051
4
o
0052
52
1109
209
1318
4
o
0065
65
1369
240
1609
4
o
0077
77
1479
251
1730
4
o
0096
96
1715
290
2005
4
o
0124
124
2256
362
2618
4
o
0156
156
2857
421
3278
4
o
0180
180
3316
482
3798
4
o
0216
216
3720
587
4307
4
o
0240
240
3897
600
4497
4
o
0302
302
5202
857
6059
4
o
0361
361
5434
863
6297
4
o
0414
414
6444
1012
7456
A.3 Drive Watt Loss Data
270