4.5 Pump Application Presets
The following sections list the parameters affected by the different Application Presets.
Note:
Setting A1-03 to 6011 or 6012 changes the Quick Start and Preset parameters (tables below) and also changes HAND Mode so that it is no
longer lower-limited by the minimum pump frequency or the thrust frequency. Also, the default for P1-06 when in RPM mode is 1800 RPM
instead of 2400 RPM.
u
Modified Parameters Depending on A1-03 Setting
The following tables show the parameters that are set depending on the A1-03 initialization:
A1-03 = 6008
(A1-06 = 8)
Pressure Control
A1-03 = 6009
(A1-06 = 9)
Pump Down Level
A1-03 = 6011
(A1-06 = 11)
VTC Pressure Control
A1-03 = 6012
(A1-06 = 12)
Pivot Panel VTC
Parameter
Value
Parameter
Value
Parameter
Value
Parameter
Value
A1-02
0
A1-02
0
A1-02
0
A1-02
0
b5-09
1
b1-03
1
b1-02
1
b5-39
2
b5-03
5.0
b1-03
0
P1-02
6
C1-01
15.0 s
b5-03
5.0 s
P2-01
2
C1-02
15.0 s
C1-01
20.0 s
P2-23
0.00%
E1-04
65.0 Hz
C1-02
20.0 s
E2-04
4
E1-04
65.0 Hz
L2-01
0
E2-04
4
L5-01
0
L2-01
0
P1-03
100.0 PSI
L5-01
0
P1-06
35.0 Hz
L5-04
300.0 s
P2-03
15 s
P1-03
200.0 PSI
P2-23
0.00%
P1-06
35.0 Hz
P3-50
35.0 Hz
P1-11
210.0 PSI
P3-60
35.0 Hz
P1-40
60.0 Hz
P3-70
35.0 Hz
P2-03
15 s
P4-12
0.0 Hz
P2-23
0.00%
P5-02
6.0 Hz
P4-12
0.0 Hz
Q5-03
40.0 PSI
P5-01
0
Q5-06
50.0 PSI
P5-02
6.0 Hz
Q5-09
20.0 PSI
Q5-10
5.0 min
Q5-11
2
Q5-16
1.00
Q5-17
3.0 s
H2-01
80H
H2-02
81H
H2-03
82H
P1-40
60.0 Hz
P3-01
2
P3-04
5.0 PSI
P3-06
5.0 Hz
P3-07
7.0 s
P3-10
2.0 PSI
4.5 Pump Application Presets
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
101