Harmonic Filter Modules
Table D.9 Harmonic Filter Module Closed-Loop Crimp Terminal Size
Drive Model
Wire Gauge
(AWG, kcmil)
Screw
Size
Crimp Terminal
Model Number
Tool
Insulation Cap
Model No.
R/L1, S/L2, T/L3
X, Y, Z
Machine No.
Die Jaw
EUJ71180
o
.
o
1/0
M12
R60-12
YF-1
YET-300-1
TD-321
TD-311
TP-060
100-066-160
2/0
70-12
TD-322
TD-311
TP-080
100-054-036
4/0
R100-12
TD-324
TD-312
TP-100
100-051-270
250
R150-12
TD-325
TD-313
TP-150
100-051-273
R150-12
TP-150
100-051-273
EUJ71181
o
.
o
1/0
M12
R60-12
YF-1
YET-300-1
TD-321
TD-311
TP-060
100-066-160
2/0
70-12
TD-322
TD-311
TP-080
100-054-036
3/0
80-12
TD-323
TD-312
TP-080
100-051-268
R100-12
TD-324
TD-312
TP-100
100-051-270
250
R150-12
TD-325
TD-313
TP-150
100-051-273
300
R150-12
TP-150
100-051-273
EUJ71182
o
.
o
1/0
M12
R60-12
YF-1
YET-300-1
TD-321
TD-311
TP-060
100-066-160
2/0
70-12
TD-322
TD-311
TP-080
100-054-036
R100-12
TD-324
TD-312
TP-100
100-051-270
250
R150-12
TD-325
TD-313
TP-150
100-051-273
30
R150-12
TP-150
100-051-273
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
<2> Recommended wire gauges. Refer to local codes for proper selections.
Note:
Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C (167 °F) 600 Vac UL-approved vinyl-sheathed insulation.
n
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external
power supply shall be a UL Listed Class 2 power supply source or equivalent only.
Table D.10 Control Circuit Terminal Power Supply
Input / Output
Terminal Signal
Power Supply Specifications
Open Collector Outputs
DM+, DM-
Requires class 2 power supply
Digital Inputs
S1 to S8, SN, SC, SP, HC, H1, H2
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
Analog Inputs / Outputs
+V, -V, A1, A2, A3, AC, AM, FM
Pulse Train Input
RP, AC
Pulse Train Output
MP, AC
n
Drive Short Circuit Rating
The drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vac
maximum (200 V Class) and 480 Vac maximum (400 V class: 4E
oooo
and 4W
oooo
), and 500 Vac maximum (400 V
class: 4A
oooo
and 4P
oooo
) with built-in fuses manufactured by Hinode Electric Co., Ltd. and Mersen (or equivalent).
n
Branch Circuit Protection
For installation in the United States, branch circuit protection must be provided in accordance with the National Electrical
Code (NEC) and any applicable local codes. To fulfill this requirement, use the UL classified fuses.
For installation in Canada, branch circuit protection must be provided in accordance with the Canadian Electrical Code and
any applicable provincial codes. To fulfill this requirement, use the UL classified fuses.
D.3 UL and CSA Standards
668
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Содержание U1000 iQpump Drive
Страница 705: ......