u
E3-01 (Motor 2 Control Mode) Dependent Parameters
Table B.5 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
No.
Name
Setting Range
Resolution
Control Modes (E3-01)
V/f (0)
V/f w/PG (1)
OLV (2)
CLV (3)
C3-21
Motor 2 Slip Compensation Gain
0.0 to 2.5
0.1
0.0
–
1.0
1.0
C3-22
Motor 2 Slip Compensation Primary Delay
Time
0 to 10000
1 ms
2000
–
200
–
C5-21
Motor 2 ASR Proportional Gain 1
0.00 to 300.00
0.01
–
0.20
–
20.00
C5-22
Motor 2 ASR Integral Time 1
0.000 to 10.000
0.001 s
–
0.200
–
0.500
C5-23
Motor 2 Proportional Gain 2
0.00 to 300.00
0.01
–
0.02
–
20.00
C5-24
Motor 2 ASR Integral Time 2
0.000 to 10.000
0.001 s
–
0.050
–
0.500
C5-26
Motor 2 Carrier Frequency Selection
1 to 4; F
–
7
E3-04
Motor 2 Maximum Output Frequency
40.0 to 400.0
0.1 Hz
60.0
60.0
60.0
60.0
E3-05
Motor 2 Maximum Output Voltage
0.0 to 255.0
0.1 V
200.0
200.0
200.0
200.0
E3-06
Motor 2 Base Frequency
0.0 to 400.0
0.1 Hz
60.0
60.0
60.0
60.0
E3-07
Motor 2 Mid Output Frequency
0.0 to 400.0
0.1 Hz
3.0
3.0
3.0
0.0
E3-08
Motor 2 Mid Output Frequency Voltage
0.0 to 255.0
0.1 V
15.0
15.0
11.0
0.0
E3-09
Motor 2 Minimum Output Frequency
0.0 to 400.0
0.1 Hz
1.5
1.5
0.5
0.0
E3-10
Motor 2 Minimum Output Voltage
0.0 to 255.0
0.1 V
9.0
9.0
2.0
0.0
<1> Default setting is determined by parameters o2-04, Drive Model Selection, and C6-01, Drive Duty Selection.
<2> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
B.16 Control Mode Dependent Parameter Default Values
586
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Содержание U1000 iQpump Drive
Страница 705: ......