B.15 U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
u
U1: Operation Status Monitors
No.
(Addr.
Hex)
Name
Description
Analog
Output Level
Unit
U1-01
(0040) Frequency Reference
Frequency Ref
All Modes
Monitors the frequency reference. Display units are determined
by o1-03.
10 V: Max
frequency
(-10 to +10 V)
0.01 Hz
U1-02
(0041) Output Frequency
Output Freq
All Modes
Displays the output frequency. Display units are determined by
o1-03.
10 V: Max
frequency
(-10 to +10 V)
0.01 Hz
U1-03
(0042) Output Current
Output Current
All Modes
Displays the output current.
10 V: Drive
rated current
U1-04
(0043) Control Method
Control Method
All Modes
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
No signal output
available
–
U1-05
(0044) Motor Speed
Motor Speed
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Displays the motor speed feedback. Display units are determined
by o1-03.
10 V: Max
frequency
(-10 to +10 V)
0.01 Hz
U1-06
(0045)
Output Voltage
Reference
Output Voltage
All Modes
Displays the output voltage.
10 V: 200 Vrms
0.1 Vac
U1-07
(0046) Control Circuit Voltage DC Bus Voltage
All Modes
Displays the control circuit voltage.
10 V: 400 V
1 Vdc
U1-08
(0047) Output Power
Output kWatts
All Modes
Displays the output power (this value is calculated internally).
(-10 to +10 V)
U1-09
(0048) Torque Reference
Torque Reference
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
OLV
CLV/PM
CLV
Monitors the internal torque reference.
10 V: Motor
rated torque
(-10 to +10 V)
0.1%
U1-10
(0049) Input Terminal Status
Input Term Sts
All Modes
Displays the input terminal status.
U1 - 10=
00000000
Digital input 1
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
Digital input 8
(terminal S8 enabled)
1
1
1
1
1
1
1
1
No signal output
available
–
B.15 U: Monitors
572
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual