B.8 F: Option Settings
F parameters program the drive for PG feedback from the motor and to function with option cards.
u
F1: PG Speed Control Card Settings (PG-B3, PG-X3, PG-RT3, PG-F3)
Parameters F1-01, F1-05, F1-06, F1-12, F1-13, and F1-18 through F1-21 include “PG 1” in the parameter name and are used
to set up a PG option card plugged into option port CN5-C of the drive.
Parameters F1-31 through F1-37 include “PG 2” in the parameter name and are used to set up a PG option card plugged into
option port CN5-B of the drive.
Other parameters in the F1 group are used to set operation for PG options plugged into port CN5-C and CN5-B.
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
F1-01
(0380)
PG 1 Pulses Per
Revolution
PG1 Pulses/Rev
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
CLV/PM
CLV
Sets the number of PG (pulse generator or encoder) pulses. Sets
the number of pulses per motor revolution.
Note:
Setting range is 0 to 15000 ppr when A1-02 = 7
(CLV/PM control mode).
Default: 1024 ppr
Min.: 1
Max.: 60000
F1-02
(0381)
Operation Selection at
PG Open Circuit (PGo)
PG Fdbk Loss Sel
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Not Detect
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
CLV/PM
CLV
0: Ramp to stop. Decelerate to stop using the deceleration time
in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in
C1-09.
3: Alarm only.
4: No alarm display
Note:
Depending on motor speed and load conditions,
an oC error may occur.
Default: 1
Range: 0 to 4
F1-03
(0382)
Operation Selection at
Overspeed (oS)
PG Overspeed Sel
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
CLV/PM
CLV
0: Ramp to stop. Decelerate to stop using the deceleration time
in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in
C1-09.
3: Alarm only.
Note:
In AOLV/PM, the motor will coast to a stop
(F1-03 = 1). The setting for F1-03 cannot be
changed to 0, 2, or 3.
Default: 1
Range: 0 to 3
F1-04
(0383)
Operation Selection at
Speed Deviation (dEv)
PG Deviation Sel
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
AOLV/PM
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
AOLV/PM
CLV/PM
CLV
0: Ramp to stop. Decelerate to stop using the deceleration time
in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in
C1-09.
3: Alarm only.
Default: 3
Range: 0 to 3
F1-05
(0384)
PG 1 Rotation Selection
PG1 Rotation Sel
0: Fwd = C.C.W
1: Fwd = C.W.
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
CLV/PM
CLV
0: Pulse A leads
1: Pulse B leads
Range: 0, 1
F1-06
(0385)
PG 1 Division Rate for
PG Pulse Monitor
PG1 Output Ratio
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
CLV/PM
CLV
Sets the division ratio for the pulse monitor used of the PG
option card installed to port CN5-C.
When setting for a three-digit number “xyz”, the division ratio
becomes = [(1 + x) / yz].
If only using the A pulse for one-track input, the input ratio will
be 1:1 regardless of F1-06 setting.
Default: 1
Min.: 1
Max.: 132
B.8 F: Option Settings
522
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual