<2> Display is in the following units:
u
E5: PM Motor Settings
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
E5-01
(0329)
Motor Code Selection
(for PM Motors)
PM Mtr Code Sel
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
CLV/PM
OLV/PM
AOLV/PM
CLV/PM
Enter the Yaskawa motor code for the PM motor being used.
Various motor parameters are automatically set based on the
value of this parameter. Settings that were changed manually
will be overwritten by the defaults of the selected motor code.
Note:
1. Set to FFFF when using a non-Yaskawa PM
motor or a special motor.
2. If an alarm or hunting occurs despite using a
motor code, enter the value indicated on the
nameplate.
Permanent Magnet Motors on page 158
details.
Min.: 0000
Max.: FFFF
E5-02
(032A)
Motor Rated Power (for
PM Motors)
PM Mtr Capacity
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
CLV/PM
OLV/PM
AOLV/PM
CLV/PM
Sets the rated capacity of the motor.
Min.: 0.10 kW
Max.: 650.00 kW
E5-03
(032B)
Motor Rated Current (for
PM Motors)
PM Mtr Rated FLA
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
CLV/PM
OLV/PM
AOLV/PM
CLV/PM
Sets the motor rated current.
Min: 10% of
drive rated
current
Max: 150% of
drive rated
current
E5-04
(032C)
Number of Motor Poles
(for PM Motors)
PM Motor Poles
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
CLV/PM
OLV/PM
AOLV/PM
CLV/PM
Sets the number of motor poles.
Min.: 2
Max.: 48
E5-05
(032D)
Motor Stator Resistance
(r1) (for PM Motors)
PM Mtr Arm Ohms
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
CLV/PM
OLV/PM
AOLV/PM
CLV/PM
Set the resistance for each motor phase.
Min.: 0.000 Ω
Max.: 65.000 Ω
E5-06
(032E)
Motor d-Axis
Inductance (Ld) (for PM
Motors)
PM Mtr d Induct
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
CLV/PM
OLV/PM
AOLV/PM
CLV/PM
Sets the d-Axis inductance for the PM motor.
Min.: 0.00 mH
Max.: 300.00 mH
E5-07
(032F)
Motor q-Axis
Inductance (Lq) (for PM
Motors)
PM Mtr q Induct
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
CLV/PM
OLV/PM
AOLV/PM
CLV/PM
Sets the q-Axis inductance for the PM motor.
Min.: 0.00 mH
Max.: 600.00 mH
E5-09
(0331)
Motor Induction Voltage
Constant 1 (Ke) (for PM
Motors)
PM Mtr Ind V 1
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
CLV/PM
OLV/PM
AOLV/PM
CLV/PM
Sets the induced phase peak voltage in units of 0.1 mV/(rad/s)
[electrical angle]. Set this parameter when using a Yaskawa
SSR1-Series PM motor with derated torque, or a Yaskawa
SST4-Series motor with constant torque.
Set E5-24 to 0 when setting this parameter.
Min.: 0.0 mV/
(rad/s)
Max.: 2000.0
mV/
(rad/s)
E5-11
(0333)
Encoder Z Pulse Offset
(
Δθ
) (for PM Motors)
Enc Z-Pulse Offs
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
CLV/PM
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
CLV/PM
Sets the offset between the rotor magnetic axis and the Z Pulse
of an incremental encoder during Z Pulse offset tuning.
Default: 0.0 deg
Min.: -180
Max.: 180
E5-24
(0353)
Motor Induction Voltage
Constant 2 (Ke) (for PM
Motors)
PM Mtr Ind V 2
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
CLV/PM
OLV/PM
AOLV/PM
CLV/PM
Sets the induced phase-to-phase rms voltage in units of 0.1 mV/
(r/min) [mechanical angle]. Set this parameter when using a
Yaskawa SMRA-Series SPM motor.
Min.: 0.0 mV/
(r/min)
Max.: 6500.0
mV/
(r/min)
B.7 E: Motor Parameters
520
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual