No.
(Addr
Hex.)
Name
LCD Display
Description
Values
Page
b3-53
(0BCA)
Backspin Search
Deceleration Time 2
BkspinSrchDecel2
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
OLV
Sets the search frequency deceleration rate for a Speed Search
from the opposite direction of the direction command when the
momentary power loss time is equal to or longer than the time
set in b3-51.
Default: 2.0 s
Min.: 0.1
Max.: 10.0
<1> Default setting is determined by parameter A1-02, Control Method Selection.
<2> Default setting is determined by parameter o2-04, Drive Model Selection.
<3> Default setting is determined by parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<4> Available in drive software versions PRG: 1017 and later.
<5> Setting range is determined by o2-04, Drive Model Selection.
u
b4: Timer Function
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
b4-01
(01A3)
Timer Function On-
Delay Time
Delay-ON Timer
All Modes
Sets the on-delay and off-delay times for a digital timer output
(H2-
oo
= 12).
The output is triggered by a digital input programmed to
H1-
oo
= 18).
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
b4-02
(01A4)
Timer Function Off-
Delay Time
Delay-OFF Timer
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
b4-03
(0B30) H2-01 ON Delay Time
H2-01 ON Delay
All Modes
Sets the length of the delay time for contact outputs to open or
close for the related functions set in H2-
oo
.
Default: 0 ms
Min.: 0
Max.: 65000
b4-04
(0B31) H2-01 OFF Delay Time H2-01 OFF Delay
b4-05
(0B32) H2-02 ON Delay Time
H2-02 ON Delay
b4-06
(0B33) H2-02 OFF Delay Time H2-02 OFF Delay
b4-07
(0B34) H2-03 ON Delay Time
H2-03 ON Delay
b4-08
(0B35) H2-03 OFF Delay Time H2-03 OFF Delay
B.4 b: Application
498
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Содержание U1000 iQpump Drive
Страница 705: ......