Cause
Possible Solutions
Incorrect frequency reference setting.
• Check the multi-function analog input settings. Multi-function analog input terminal A1, A2,
or A3 is set for frequency gain (H3-02, H3-10, or H3-06 is set to “1”), but there is no voltage
or current input provided.
• Make sure H3-02, H3-10, and H3-06 are set to the proper values.
• See if the analog input value is set to the right value (U1-13 to U1-15).
The Stall Prevention level during acceleration and
deceleration set too low.
• Check the Stall Prevention level during acceleration (L3-02).
• If L3-02 is set too low, acceleration may be taking too long.
• Increase L3-02.
The Stall Prevention level during run has been set too
low.
• Check the Stall Prevention level during run (L3-06).
• If L3-06 is set too low, speed will drop as the drive outputs torque.
• Increase the setting value.
Drive reached the limitations of the V/f motor control
method.
• The motor cable may be long enough (over 50 m) to require Auto-Tuning for line-to-line
resistance.
• Be aware that V/f Control is comparatively limited when it comes to producing torque at low
speeds.
• Consider switching to Open Loop Vector Control.
u
Drive Frequency Reference Differs from the Controller Frequency Reference Command
Cause
Possible Solutions
The analog input gain and bias for the frequency
reference input are set to incorrect values.
• Check the gain and bias settings for the analog inputs that are used to set the frequency reference.
Check parameters H3-03 and H3-04 for input A1, check parameters H3-11, and H3-12 for input
A2, and check parameters H3-07 and H3-08 for input A3.
• Set these parameters to the appropriate values.
A frequency bias signal is being entered via analog
input terminals A1 to A3.
• If more than one of multi-function analog inputs A1 to A3 is set for frequency reference bias
(H3-02, H3-10, or H3-06 is set to “0”), then the sum of all signals builds the frequency reference.
• Make sure that H3-02, H3-10, and H3-06 are set appropriately.
• Check the input level set for terminals A1 to A3 (U1-13 to U1-15).
PID control is enabled, and the drive is consequently
adjusting the output frequency to match the PID
setpoint. The drive will only accelerate to the
maximum output frequency set in E1-04 while PID
control is active.
If PID control is not necessary for the application, disable it by setting b5-01 to 0.
u
Excessive Motor Oscillation and Erratic Rotation
Cause
Possible Solutions
Poor balance between motor phases.
Check drive input power voltage to ensure that it provides stable power.
Hunting prevention function is disabled.
• Enable Hunting Prevention (n1-01 = 1).
• Increase the AFR gain (n2-01) or the AFR time constant 1 (n2-02).
u
Noise From Drive or Motor Cables When the Drive is Powered On
Cause
Possible Solutions
Relay switching in the drive generates excessive noise.
• Lower the carrier frequency (C6-02).
• Install a noise filter on the input side of drive input power.
• Install a noise filter on the output side of the drive.
• Place the wiring inside a metal conduit to shield it from switching noise.
• Ground the drive and motor properly.
• Separate the main circuit wiring and the control lines.
• Make sure wires and the motor have been properly grounded.