Digital Operator Display
Error Name
One of the following settings was entered while H1-
oo
= 2 (External
Reference 1/2):
• b1-15 = 4 (Pulse Train Input) but the pulse train input selection is not set
for the frequency reference (H6-01 > 0)
• b1-15 or b1-16 set to 3 but no option card is connected
• Although b1-15 = 1 (Analog Input) and H3-02 or H3-10 are set to 0
(Frequency Bias)
Correct the settings for the multi-function input terminal parameters.
H2-
oo
is set to 38 (Drive Enabled) and H1-
oo
is not set to 6A (Drive
Enable).
H1-
oo
is set to 7E (Direction Detection) and H6-01 is not set to 3 (for V/f
Control with PG using terminal RP as speed feedback input).
H1-
oo
is set to 16 when using PG-RT3.
Correct the setting. PG-RT3 is not available for the application with Motor
2 selection.
Digital Operator Display
Error Name
oPE04
Initialization Required
Cause
Possible Solutions
The drive, control board, or terminal board have been replaced and the
parameter settings between the control board and the terminal board no
longer match.
Set A1-03 to 5550 to load the parameter settings stored in the terminal board
to the drive. Initialize parameters after drive replacement by setting A1-03
to 2220 or 3330.
Digital Operator Display
Error Name
oPE05
Run Command/Frequency Reference Source Selection Error
Cause
Possible Solutions
Frequency reference is assigned to an option card (b1-01 = 3) and an input
option card is not connected to the drive.
Reconnect the input option card to the drive.
The Run command is assigned to an option card (b1-02 = 3) and an input
option card is not connected to the drive.
Frequency reference is assigned to the pulse train input (b1-01 = 4) and
terminal RP is not set for frequency reference input (H6-01 > 0)
Set H6-01 to 0.
Although the digital card input is set for BCD special for a 5-digit input
(F3-01 = 6), the data length is set for 8-bit or 12-bit (F3-03 = 0, 1).
Set F3-03 to 2 to set the input data for 16-bit.
The following values have been set while an AI-A3 option card is installed:
• The source of frequency reference setting is assigned to an option card
(b1-01 = 3).
• The action for the analog card is set for separate terminal input
(F2-01 = 0).
Properly set parameters.
Digital Operator Display
Error Name
oPE06
Control Method Selection Error
Correct the setting for the control method.
Cause
Possible Solutions
A control mode has been selected that requires a PG option card to be
installed, but no PG encoder is installed (A1-02 = 1, 3, or 7).
• Connect a PG option card.
• Correct the value set to A1-02.
Digital Operator Display
Error Name
oPE07
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02,
H3-10, or H3-06 and PID functions conflict.
Cause
Possible Solutions
At least two analog input terminals are set to the same function (i.e., at least
two of these parameters have the same setting: H3-02, H3-10, or H3-06).
Change the settings to H3-02, H3-10, and H3-06 so that functions no longer
conflict.
Note:
Both 0 (Frequency Reference Bias) and F (Not Used) can be
set to H3-02, H3-10, or H3-06 simultaneously.
6.6 Operator Programming Errors
394
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual