L4-04
L4-04
Frequency
reference
Speed Agree 2
ON
OFF
ON
OFF
Output Frequency
Figure 5.72 Speed Agree 2 Time Chart
Refer to L4-03, L4-04: Speed Agree Detection Level and Detection Width (+/-) on page 321
Setting 14: User-Set Speed Agree 2 (f
ref
/f
set
Agree 2)
The output closes when the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within
the speed agree width (L4-04) of the programmed speed agree level (L4-03).
Status
Description
Open
Output frequency or motor speed and frequency reference are both outside the range of L4-03 ±L4-04.
Closed
Output frequency or motor speed and the frequency reference are both within the range of L4-03 ±L4-04.
Note:
The detection level L4-03 is a signed value; detection works in the specified direction only.
Frequency reference
+
L4-04
Frequency reference
– L4-04
L4-03
L4-03
+
L4-04
L4-03
– L4-04
Frequency
reference
0 Hz
OFF
OFF
ON
ON
Frequency reference
During
Forward
Output frequency
Output frequency
User Set
Speed Agree 2
Figure 5.73 User-Set Speed Agree 2 Example with a Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agree Detection Level and Detection Width (+/-) on page 321
Setting 15: Frequency Detection 3
The output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-03 plus
the detection with set in L4-04. The terminal remains open until the output frequency or motor speed falls below the level set
in L4-03. The detection level L4-03 is a signed value; detection works in the specified direction only.
Status
Description
Open
Output frequency or motor speed exceeded L4-03 plus L4-04.
Closed
Output frequency or motor speed is below L4-03 or has not exceeded L4-03 plus L4-04.