![YASKAWA U1000 iQpump Drive Скачать руководство пользователя страница 258](http://html1.mh-extra.com/html/yaskawa/u1000-iqpump-drive/u1000-iqpump-drive_technical-manual_3309131258.webp)
Set the Motor Iron Loss for Torque Compensation
Only required when using V/f Control. Enter this value in watts to E2-10. The drive uses this setting to improve the precision
of torque compensation.
u
E3: V/f Pattern for Motor 2
These parameters set the V/f pattern used for motor 2.
Refer to Setting 16: Motor 2 Selection on page 282
for details on
switching motors.
Note:
The function for switching between two motors cannot be used with a PM motor. E3-
oo
parameters are hidden when a PM motor control
mode is selected (A1-02 = 5, 6, or 7).
n
E3-01: Motor 2 Control Mode Selection
Selects the control mode for motor 2. A control mode for PM motors cannot be selected for motor 2.
No.
Parameter Name
Setting Range
Default
E3-01
Motor 2 Control Mode Selection
0 to 3
0
Note:
L1-01 determines protection from motor overload (oL1) in motor 2 and motor 1.
Setting 0: V/f Control
Setting 1: V/f Control with PG
Setting 2: Open Loop Vector Control
Setting 3: Closed Loop Vector Control
n
E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 as shown in
.
Note:
Certain E3-
oo
parameters might not be visible depending on the control mode.
Refer to Parameter List on page 489
for details.
No.
Parameter Name
Setting Range
Default
E3-04
Motor 2 Max Output Frequency
40.0 to 400.0 Hz
E3-05
Motor 2 Max Voltage
E3-06
Motor 2 Base Frequency
0.0 to [E3-04]
E3-07
Motor 2 Mid Output Frequency
0.0 to [E3-04]
E3-08
Motor 2 Mid Output Frequency Voltage
E3-09
Motor 2 Minimum Output Frequency
0.0 to [E3-04]
E3-10
Motor 2 Minimum Output Frequency Voltage
E3-11
Motor 2 Mid Output Frequency 2
0.0 to [E3-04]
0.0 Hz
E3-12
Motor 2 Mid Output Frequency Voltage 2
E3-13
Motor 2 Base Voltage
<1> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
<2> Default setting is determined by the control mode selected for motor 2 (E3-01).
<3> The drive sets this value when Auto-Tuning is performed (Rotational Auto-Tuning and Stationary Auto-Tuning 2).
<4> Parameter ignored when E3-11 and E3-12 are set to 0.0.
5.5 E: Motor Parameters
258
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Содержание U1000 iQpump Drive
Страница 705: ......