b1-07: LOCAL/REMOTE Run Selection
The drive has three separate control sources that can be switched using digital inputs (H1-
oo
= 1 (LOCAL/REMOTE
Selection) or 2 (External reference 1/2)) or the LO/RE key on the digital operator.
Refer to Setting 1: LOCAL/REMOTE
,
Refer to Setting 2: External Reference 1/2 Selection on page 278
(LOCAL/REMOTE) Key Function Selection on page 345
for details.
• LOCAL: Digital operator. The digital operator sets the frequency reference and Run command.
• REMOTE: External reference 1. The frequency reference and Run command source are set by b1-01 and b1-02.
• REMOTE: External reference 2. The frequency reference and Run command source are set by b1-15 and b1-16.
When switching from LOCAL to REMOTE, or between External reference 1 and External reference 2, the Run command
may already be present at the location at which the source is being switched. In this case, use parameter b1-07 to determine
how the Run command is treated.
No.
Parameter Name
Setting Range
Default
b1-07
LOCAL/REMOTE Run Selection
0, 1
0
Setting 0: Run command must be cycled
When the Run command source differs between the old source and the new source (e.g., the old source was the terminals and
the new source is serial communication), and the Run command is active at the new source as the switchover occurs, the drive
will not start or the drive will stop operation if it was previously running. The Run command must be cycled at the new source
to restart the drive.
Setting 1: Accept Run command at the new source
When the Run command is active at the new source, the drive starts or continues operation if it was previously running.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel
from rotating machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.
n
b1-08: Run Command Selection while in Programming Mode
As a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being used
to adjust parameters in Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-Tuning Mode).
If required by the application, set b1-08 to allow the drive to run while in Programming Mode.
No.
Parameter Name
Setting Range
Default
b1-08
Run Command Selection while in Programming Mode
0 to 2
0
Setting 0: Disabled
A Run command is not accepted while the digital operator is in Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit programming during run
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
n
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
No.
Parameter Name
Setting Range
Default
b1-14
Phase Order Selection
0, 1
0
Setting 0: Standard Phase Order
Setting 1: Switched Phase Order (A1-02 = 0, 1, 2, 3, 5, 6)
n
b1-15: Frequency Reference Selection 2
Enabled when H1-
oo
= 2 and the terminal is closed.
Refer to Setting 2: External Reference 1/2 Selection on page 278
and
Refer to b1-02: Run Command Selection 1 on page 188
No.
Parameter Name
Setting Range
Default
b1-15
Frequency Reference Selection 2
0 to 4
0
5.2 b: Application
194
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual