5.10 o: Operator Related Settings
216
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
■
o2-06: Operation Selection when Digital LCD Operator is Disconnected
Determines if the drive will stop when an external LCD operator is removed in LOCAL mode or with b1-02 set to 0.
Note:
An LCD operator is available as an option. This setting is not applicable to the standard LED operator that comes with the drive.
Setting 0: Continue Operation
The operation is continued.
Setting 1: Trigger a Fault
The operation is stopped and an “oPr” fault is triggered. The motor coasts to stop.
■
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up when the Run command is set to be given
from the digital operator.
Note:
This parameter is effective only when the Run command is set to be given from the digital operator (b1-02 or b1-16 = 0).
Setting 0: Forward
Setting 1: Reverse
◆
o3: Copy Function
Use o3 parameters to Read, Copy, and Verify the parameter settings to and from the drive.
■
o3-01 Copy Function Selection
This parameter controls the copying of parameters to and from the LED operator (option). The copy function will change
certain parameter default settings depending on the regional specification of the drive.
0: COPY SELECT (no function)
1: INV --> OP READ
All parameters are copied from the drive to the LED operator.
2: OP --> INV WRITE
All parameters are copied from the LED operator to the drive.
3: OP<-->INV VERIFY
Parameter settings in the drive are compared to those in the LED operator.
Note:
When using the copy function, the drive model number (o2-04) and the software number (U1-14) must match or an error will
occur.
■
o3-02 Copy Allowed Selection
Enables and disables the digital operator copy functions.
0: Disabled
No digital operator copy functions are allowed
1: Enabled
Copying allowed
No.
Name
Setting Range
Default
o2-06
Operation Selection when Digital Operator is Disconnected
0 or 1
0
No.
Name
Setting Range
Default
o2-07
Motor Direction at Power Up when Using Operator
0 or 1
0
No.
Name
Setting Range
Default
o3-01
Copy Function Selection
0 or 1
0
No.
Name
Setting Range
Default
o3-02
Copy Allowed Selection
0, 1
0
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...