5.8 L: Protection Functions
224
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
Setting 1: Continue operation with reduced frequency reference
The drive will continue operation at the frequency reference value set in parameter L4-06. When the external frequency
reference value is restored, the operation is continued with the frequency reference.
n
L4-06: Frequency Reference at Reference Loss
Sets the frequency reference level the drive runs with when L4-05 = 1 and a reference loss was detected. The value is set
as a percentage of the frequency reference when the loss was detected.
n
L4-07: Speed Agreement Detection Selection
Determines when frequency detection is activated.
Setting 0: During run only (no detection while drive output is shut off)
Setting 1: Detection always enabled
n
L4-08: Frequency Agree Condition Selection
Sets whether a frequency agree situation should be determined by the soft-starter output frequency or by the estimated
speed of the motor.
Setting 0: Use the soft starter output frequency to determine frequency agree
Setting 1: Use the motor speed to determine frequency agree
The setting of L4-08 affects the other drive functions listed below.
• Conditions for overtorque/undertorque detection 1 and 2 (L6-01, L6-04) become so that both fault and alarm detection
for overtorque 1 and 2 (oL3, oL4) are possible only during speed agree.
• Frequency agree detection is possible with the following settings for the multi-function output terminals.
• MEMOBUS Monitor Data
• Monitor Parameter
No.
Name
Setting Range
Default
L4-06
Frequency Reference at Reference Loss
0.0 to 100.0%
80.0%
No.
Name
Setting Range
Default
L4-07
Speed Agreement Detection Selection
0 or 1
0
No.
Name
Setting Range
Default
L4-08
Frequency Agree Condition Selection
0, 1
1
Setting
Function
2
Speed Agree 1
3
User-set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
13
Speed Agree 2
14
User-set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
Register No.
Contents
002CH
Drive Status 2
bit2
Speed Agree
bit3
User Speed Agree
bit4
Frequency Detection 1
bit5
Frequency Detection 2
004BH
Drive Status (U1-12)
bit4
During Speed Agree
No.
Name
Description
U1-12
Drive Status
The 5th digit from the right indicates whether speed agree has been reached or not.
Содержание T1000A
Страница 4: ...4 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 32: ...1 5 Component Names 32 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 104: ...4 10 Test Run Checklist 104 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 334: ...7 5 Drive Replacement 334 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 362: ...A 6 Drive Derating Data 362 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...