Setting 3: 0 to 20 mA Current Input
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
n
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2.
Refer to Multi-Function Analog Input Terminal Settings
for a list of functions and descriptions.
n
H3-11, H3-12: Terminal A2 Gain and Bias Setting
Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Both can be used to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same
way as parameters H3-03 and H3-04 for analog input A1.
n
H3-13: Analog Input Filter Time Constant
Parameter H3-13 sets the time constant for a first order filter that will be applied to the analog inputs.
An analog input filter can be used to prevent erratic drive control when a “noisy” analog reference is used. The drive
operation becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing
analog signals.
n
H3-14: Analog Input Terminal Enable Selection
When one of the multi-function digital input parameters is set for “Analog input enable” (H1-
= C), the value set to
H3-14 determines which analog input terminals are enabled and which terminals are disabled when the input is closed.
All analog input terminals will be enabled all of the time if H1-
is not set to C.
Setting 1: A1 only enabled
Setting 2: A2 only enabled
Setting 3: A1 and A2 only enabled
Setting 4: A3 only enabled
Setting 5: A1 and A3 only enabled
Setting 6: A2 and A3 only enabled
Setting 7: All analog input terminals enabled
n
H3-16 to H3-18 Terminal A1/A2/A3 Offset
Parameters H3-16 to H3-18 set the offset level of the selected input value to terminal A1, A2 or A3 that is equal to 0 Vdc
input. These parameters rarely need adjustment.
No.
Name
Setting Range
Default
H3-10
Terminal A2 Function Selection
0 to 41
0
No.
Name
Setting Range
Default
H3-11
Terminal A2 Gain Setting
-999.9 to 999.9%
100.0%
H3-12
Terminal A2 Bias Setting
-999.9 to 999.9%
0.0%
No.
Name
Setting Range
Default
H3-13
Analog Input Filter Time Constant
0.00 to 2.00 s
0.03 s
No.
Name
Setting Range
Default
H3-14
Analog Input Terminal Enable Selection
1 to 7
7
No.
Name
Setting Range
Default
H3-16
Terminal A1 Offset
–500 to 500
0
H3-17
Terminal A2 Offset
–500 to 500
0
H3-18
Terminal A3 Offset
–500 to 500
0
Содержание T1000A
Страница 4: ...4 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 32: ...1 5 Component Names 32 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 104: ...4 10 Test Run Checklist 104 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 334: ...7 5 Drive Replacement 334 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 362: ...A 6 Drive Derating Data 362 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...