Modbus Map SOLECTRIA XGI 1500 (Rev A)
DOCR-XXXXXX
19 of 30
To implement the same curve, the procedure is shown below.
Write “ 4 “ to register 41072
Write “ 6030” to register 41073
Write “ 1000 to register 41074
Write “ 6080” to register 41075
Write “ 900” to register 41076
Write “ 6150” to register 41077
Write “ 600” to to register 41078
Write “ 6200” to register 41079
Write “ 0 ” to register 41080
Write “1” to register 40963 to enable Freq-Watt Control
Voltage Ride Through
10
This function allows inverter to response to low and high voltage transients that are outside the normal
operation range of the electric gird.
The image below shows the default setting of abnormal voltage trip settings. The default setting follows
IEEE1547-2014 and the function is always enabled.