Installation and Operation Guide SOLECTRIA XGI 1000
DOCR-070733-F (2/22/2021)
Page 72 of 78
Voltage and Frequency Limits and Trip Times
All models of the SOLECTRIA XGI 1000 comply with IEEE1547a-2014 requirements. The tables below show its standard
settings.
Table 11-2 Default Voltage Limits and Trip Times
VOLTAGE RANGE
VOLTAGE SETPOINT
CLEARING TIME
V < 45%
V = 45%
0.16 s
45% <= V < 60%
V = 60%
1.0 s
60% <= V < 88%
V = 88%
2.0 s
88% <= V < 110%
N/A
No trip
110% <= V <= 120%
V = 110%
1.0 s
V > 120%
V = 120%
0.16 s
Table 11-3 Frequency Limits and Trip Times
FREQUENCY RANGE
FREQUENCY SETPOINT
TRIP TIME
F < 57 HZ
F = 57 Hz
0.16 s
57 HZ <= F < 59.5 HZ
F = 59.5 Hz
2.0 s
59.5 HZ <= F < 60.5 HZ
N/A
No trip
60.5 HZ <= F <= 62 HZ
F = 60.5 Hz
2.0 s
V > 62 HZ
F = 62 Hz
0.16 s
Figure 11-1 Derating with AC Voltage