Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
DOCR-071030-A (10/7/2022)
Page 120 of 131
10.
Technical Data
Datasheet
Note 1: The “Output Voltage Range” and “Output Frequency Range may differ according to the chosen grid
standard.
MODEL NAME
PVI 25TL-208
PVI 50TL-480
PVI 60TL-480
DC INPUT
MAX. PV POWER
45kW (17kW per MPPT) 90kW (33kW per MPPT)
90kW (33kW per
MPPT)
MAX. DC INPUT VOLTAGE
1000V
DC
OPERATING DC INPUT VOLTAGE
RANGE
200-950V
DC
START-UP DC INPUT VOLTAGE /
POWER
330V / 80W
NUMBER OF MPP TRACKERS
3
MPPT VOLTAGE RANGE
480-850V
DC
540-850V
DC
MAX. PV SHORT-CIRCUIT
CURRENT
(ISC X 1.25)
135A (45A per MPPT)
204A (68A per MPPT)
NUMBER OF DC INPUTS
6 inputs, 2 per MPPT
15 inputs, 5 per MPPT
DC DISCONNECTION TYPE
Load-rated DC switch
DC SURGE PROTECTION
Type II MOV, 1240V
C
, 15kA I
TM
(8/20
μ
S)
AC OUTPUT
RATED AC OUTPUT POWER
25kW
50kW
60kW
MAX. AC APPARENT POWER
25kVA
50kVA/55kVA
60kVA/66kVA
RATED OUTPUT VOLTAGE
208V
AC
480V
AC
OUTPUT VOLTAGE RANGE
183-229V
AC
422-528V
AC
GRID CONNECTION TYPE
3Φ/PE/N (
Physical Neutral optional)
MAX. AC OUTPUT CURRENT
@480V
AC
69.5A@208VAC
60.2A/66.2A@480VAC
72.2A/79.4A@480VAC
MAX AC OCPD RATING
125A
Suggested 110A
Actual 153A
Suggested 125A
Actual 153A
RATED OUTPUT FREQUENCY
60Hz
OUTPUT FREQUENCY RANGE
1
57-63Hz
POWER FACTOR
>0.99 (±0.8 adjustable)
CURRENT THD
<3%
MAX. FAULT CURRENT
CONTRIBUTION (1 CYCLE RMS)
64.1A
AC DISCONNECTION TYPE
Load-rated AC switch
AC SURGE PROTECTION
Type II MOV, 1240V
C
, 15kA I
TM
(8/20
μ
S)