Command
Index:Sub
Name
Type
Offset
Access Default
Description
0x2000:00
Command
U8
0
ro
3
Command Object
(complete access is not possible)
0x2000:01
Execute Com-
mand
U32
16
rw
0
Execute Command
n
0x00000000: Clear all values in object
0x2000
n
0x00000001: Reset FMM data
n
0x00004001: Read web server state
–
Parameter
in 0x2000:02
n
0x00008001: Set web server state
–
Parameter
in 0x2000:02
0x2000:02
Parameter
U32
48
ro
0
Additional parameter for command execution
State web server
n
1: enable
n
0: disable
Will be stored permanently
0x2000:03
Status
U32
80
ro
0
Return value of command execution:
n
0: initial state
n
1: command executed
n
2: command not executed
n
3: command unknown
n
4: command not executable in this state
‘Explanation of the elements’ page 82
System SLIO
Deployment
Object Dictionary
HB300 | IM | 053-1EC01 | en | 22-30