10 Output Assemblies (Converter Consumes)
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
67
Name
Description
D1000: Run
R1000: Auto Run
D1000: Run converter
0: Stop
1: Run
R1000: Run converter in auto
0: Stop
1: Auto Run
Fault Reset
Fault Reset
0: -
1: Fault Reset
D1000: Voltage Reference (High Byte)
R1000: -
D1000: Voltage Reference
Sets converter voltage reference.
Voltage reference data: Voltage reference/2VS (VS: Voltage scale)
Setting range: 0 - FFFF (Hex.)
Example: setting a reference of 4096 with a voltage scale of 2:
Voltage reference data = 4096/2
2
= 1024 = 400 (Hex.)
Unit depends on
o1-03
.
R1000: -
◆
EtherNet/IP Extended Speed Control Output - 21 (0x15)
Output Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
21
0
0
-
D1000:
NetRef
R1000: -
NetCtrl
-
-
Fault Reset
D1000: -
R1000:
Forced Run
D1000: Run
R1000: Auto
Run
1
-
1
2
D1000: Voltage Reference (Low Byte)
R1000: -
3
D1000: Voltage Reference (High Byte)
R1000: -
Name
Description
D1000: Run
R1000: Auto Run
D1000: Run converter
0: Stop
1: Run
R1000: Run converter in auto
0: Stop
1: Auto Run
D1000: -
R1000: Forced Run
D1000: -
R1000: Force run converter
0: Stop
1: Force Run
Fault Reset
Fault Reset
0: -
1: Fault Reset
NetCtrl
Run command from network
0: Depends on
b1-02
1: Run Command is from network
D1000: NetRef
R1000: -
D1000: Voltage command from network
0: Depends on
b1-01
1: Voltage command from network
R1000: -
D1000: Voltage Reference
R1000: -
D1000: Voltage Reference
Sets converter voltage reference.
Voltage reference data: Voltage reference/2VS (VS: Voltage scale)
Setting range: 0 - FFFF (Hex.)
Example: setting a reference of 4096 with a voltage scale of 2:
Voltage reference data = 4096/2
2
= 1024 = 400 (Hex.)
Unit depends on
o1-03
.
R1000: -