9 Input Assemblies (Drive Produces)
YASKAWA
SIEP C730600 0DB EtherNet/IP Technical Manual
65
Name
Description
0: M5/M6 OFF
1: M5/M6 ON
This function is enabled only when H2-03 is set to F.
Note:
The names of the digital outputs are different for different drive series.
Output Frequency
Actual Drive Speed
Monitors drive output frequency.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Dynamic Inputs
Contains the data to be read from the MEMOBUS/Modbus address defined in the given parameter. A value of 0 in the given
parameter means it will return the default data as defined in the table above.
◆
(Vendor Specific Yaskawa Electric (YE) Assy) 24-Byte Dynamic Input - 170
(0xAA)
Input Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
170
0
0
Faulted
Alarm
Ready
Speed Agree
Fault Reset
REV Running
ZSP
Running
1
ZSV
-
Multi-
Function
Digital
Output 3
Multi-
Function
Digital
Output 2
Multi-
Function
Digital
Output 1
LOCAL/
REMOTE
Uv
oPE
1
2
Output Frequency (Low Byte)
3
Output Frequency (High Byte)
2
4 - 5
Dynamic Input 1 [F7-33], Default: Fault Code
3
6 - 7
Dynamic Input 2 [F7-34], Default: Output Power [U1-08]
4
8 - 9
Dynamic Input 3 [F7-35], Default: Analog Input 2
5
10 - 11
Dynamic Input 4 [F7-36], Default: Digital Input
6
12 - 13
Dynamic Input 5 [F7-37], Default: Analog Input 3
7
14 - 15
Dynamic Input 6 [F7-38], Default: PG 2 Counter
8
16 - 17
Dynamic Input 7 [F7-39], Default: Net Ref and Net Ctrl
9
18 - 19
Dynamic Input 8 [F7-40], Default: Drive Software Version
10
20 - 21
Dynamic Input 9 [F7-41], Default: Not Used
11
22 - 23
Dynamic Input 10 [F7-42], Default: Not Used
Name
Description
Running
Running
0: Stop
1: Forward or Reverse Running
ZSP
Zero Speed
0: Running
1: Stop or DC Injection Braking
REV Running
Reverse Running
0: Not Reverse Running
1: Reverse Running
Fault Reset
Fault Reset
0: -
1: Fault Reset
Speed Agree
Speed Agree
0: -
1: Speed actual at speed reference
Ready
Ready
0: Not Ready
1: Ready
Alarm
Alarm
0: No Alarm
1: Alarm
Faulted
Faulted
0: No Fault
1: Fault