TOEP C730600 91B Modbus TCP/IP Installation Manual
Status
Fault Declared
Status Value (
U6-98
/
U6-99
)
Description
Connection Time-
out
bUS
1101
The control connection timer is more than
the setting value of F7-16.
Duplicate IP Address
bUS
1102
This node and at least one other node
have the same IP Address.
Default MAC
Address
-
1103
MAC Address programmed into the
option is not factory default setting.
Note:
Contact Yaskawa or your nearest
sales representative for more
information.
Two drive monitor parameters,
U6-98 [First Fault]
and
U6-99 [Current Fault]
assist the
user in network troubleshooting.
•
U6-98
displays the first declared fault since the last power cycle.
U6-98
is only cleared
upon drive power-up.
•
U6-99
displays the present option status.
U6-99
is cleared upon a network-issued fault
reset and upon power-up.
If another fault occurs while the original fault is still active, parameter
U6-98
retains the
original fault value and
U6-99
stores the new fault status value.
◆
Option Compatibility
You can connect a maximum of 3 options at the same time depending on the type of
option.
Note:
•
You can only connect one option to the GA500 and HV600 drives. Connect the option to the CN5 connector.
•
You can connect two options to an FP605 drive. Connect the communication option to the CN5-A connector.
•
Compatible communication options are different for different models. Refer to the drive manuals for more
information.
Table 9.2 Option Compatibility
Option
Connector
Number of Options
Possible
PG-B3
, PG-X3
CN5-B, C
2
PG-RT3
, PG-F3
CN5-C
1