4 CC-Link Option Components
YASKAWA ELECTRIC
SIEP C730600 22C V1000 Option CC-Link Technical Manual
11
Grounding Method Switch
The grounding method switch (S1) can change the grounding method for the CC-Link Option between common grounding and independent
grounding. Refer to
Setting Grounding Method Switch on page 13
to change the grounding method.
Note:
The grounding method switch (S1) is only available for CC-Link Options REV.B and later. Check the REV version printed on the nameplate of your CC-Link Option.
Table 4 Details on the Grounding Method Switch
Figure 5
Figure 5 Common Grounding
Figure 6
Figure 6 Independent Grounding
CC-Link Option LED Display
Table 5 CC-Link Operation LED Status
Setting Station Address
Set drive parameter F6-10 to a station address (Range 1 to 64) unique to the network. If set to 0, the L.ERR light will turn on and a Station Address
Error (AEr) will occur.
Grounding Method Switch (S1)
Terminal Name
Function
Default
FE
Changes the grounding method for the CC-Link Option between common
grounding and independent grounding.
FE (common grounding)
Name
Indication
Operating Status
Remarks
Color
Status
L.RUN
Green
ON
Normal operation
• Receiving data normally
OFF
Timed out
• Timed out waiting to receive
• Logging onto the network
• During reset
L.ERR
Red
ON
CRC error
• CRC error
• Station address setting error (F6-10 = 0)
OFF
During communications
• Normal communications
• During reset
SD
Red
ON
Sending data
• Sending data
Note:
LED may appear to flash with slower baud rates.
OFF
No data transfer
• No data being sent
• During reset
RD
Red
ON
Detecting data received
• Detecting data that was received
Note:
LED may appear to flash with slower baud rates.
OFF
Waiting for data
• Data not yet received
• During reset
NC
FE
S1
Drive
CC-Link
Option
Ground to
100
or less
Drive
CC-Link
Option
Ground to
100
or less
SIEP_C730600_22C_3_0.book 11 ページ 2022年8月23日 火曜日 午後1時4分